Shield Foam Water Sprinkler
Foam Concentrates & Equipment

Shield Foam Water Sprinkler

Shield·SKU: SHIELD-F-8000

Model No: SD-500B / SD-500S / SD-520 OPEN TYPE PENDENT TYPE FOAM WATER SPRINKLER The Foam-Water Sprinklers are used in the deluge foam system to protect the risk where foam is required to be applied from overhead sprinklers and is to be followed with plain water in a standard sprinkler pattern. Foam-Water Sprinklers protect the loading and unloading area in the event of a spill fire with low expansion foam systems. These are useful in other wide applications i.e. Air Craft Hangers, Warehousing.

Request a quote

Description

Model No: SD-500B / SD-500S / SD-520
OPEN TYPE PENDENT TYPE FOAM WATER SPRINKLER

The Foam-Water Sprinklers are used in the deluge foam system to protect the risk where foam is required to be applied from overhead sprinklers and is to be followed with plain water in a standard sprinkler pattern.

Foam-Water Sprinklers protect the loading and unloading area in the event of a spill fire with low expansion foam systems. These are useful in other wide applications i.e. Air Craft Hangers, Warehousing. Foam-Water Sprinklers are open and air aspirating type.

The pattern of coverage is similar to the conventional sprinkler head. The Foam-Water Sprinkler has standard orifice with K-factor of 42.  Foam-Water Sprinklers are designed to operate at a minimum of 2 bar pressure and maximum of 7 bar.

AUTOMATIC FOAM WATER SPRINKLER

The Sprinklers (Glass Bulb Type), Standard Orifice, Pendent type, design incorporates state-of-the-art, heat responsive, frangible glass bulb design (standard or quick response) for prompt, precise operation. The forged frame is more streamlined and attractive than traditional sand cast frames. It is cast with a hex-shaped wrench to allow easy tightening from different angles.

This sprinkler is available in various temperature ratings and finishes to meet many design requirements. All Sprinklers are manufactured using the time proven Belleville seal used exclusively by all major manufactures to ensure long life and safe operation.

Features

  • UL Listed/FM Approved.
  • Foam discharge in Spray pattern.
  • Pendant installation.
  • Specially designed for low expansion foam.
  • The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire.

Specifications

OPEN TYPE SPRINKLER CLOSED BULB SPRINKLER
Model NH-520 NH-550 NH 500, NH-500S SD1010
Material Brass, Chrome Finish

 

Brass, Chrome Finish

 

Brass, Stainless Steel
Inlet Size ½” NPT ¾” NPT

 

½” NPT ½” NPT
Max. working Pressure Max. 7 bar Max. 7 bar Max. 12 bar (175 psi) Max. 12 bar (175 psi)
Mounting Pendent Pendent Pendent Pendent
Operating Pressure 30 – 100 psi 30 – 100 psi 2.1 bar (30 psi) minimum

4.2 bar (60 psi) maximum

7 PSI
K-Factor 2.8 5 K-42 standard

 

5.6
Flow Rate 31 gpm 50 gpm 30 gpm (as per UL)

36 gpm(as per FM)

15gpm
Foam Proportioning AFFF 3% & 6%, AR-FFF 3/3, 3/6

6

Installation Height 0.9 – 4M

Catalogue family reference SHIELD-F-8000 identifies this manufacturer product page; it is not an orderable manufacturer SKU. Confirm the required model and configuration when requesting information.

Official manufacturer product information

Technical Specifications

Catalogue family referenceSHIELD-F-8000
Flow Rate31 gpm; 50 gpm; 30 gpm (as per UL) 36 gpm(as per FM); 15gpm
Foam ProportioningAFFF 3% & 6%, AR-FFF 3/3, 3/6 6
Inlet Size½” NPT; ¾” NPT; ½” NPT; ½” NPT
Installation Height0.9 – 4M
K-Factor2.8; 5; K-42 standard; 5.6
MaterialBrass, Chrome Finish; Brass, Chrome Finish; Brass, Stainless Steel
Max. working PressureMax. 7 bar; Max. 7 bar; Max. 12 bar (175 psi); Max. 12 bar (175 psi)
ModelNH-520; NH-550; NH 500, NH-500S; SD1010
MountingPendent; Pendent; Pendent; Pendent
Operating Pressure30 – 100 psi; 30 – 100 psi; 2.1 bar (30 psi) minimum 4.2 bar (60 psi) maximum; 7 PSI
Published pressure statement 1The pattern of coverage is similar to the conventional sprinkler head. The Foam-Water Sprinkler has standard orifice with K-factor of 42.  Foam-Water Sprinklers are designed to operate at a minimum of 2 bar pressure and maximum of 7 bar.

Documents & Technical Downloads