Shield Foam Chamber
Flow Control

Shield Foam Chamber

Shield·SKU: SHIELD-F-7966

Foam Chamber is used in one of the most common application to protect vertical fixed roof (cone) liquid storage tanks, with or without internal floating roof with the low expansion foam system. The application of foam is on the basis that the risk comprises the total surface area of the fuel. The foam system design guidelines generally used are in accordance with NFPA-11, standard. Foam chambers are defined by NFPA-11 as Type II discharge outlets for delivering the foam to the surface of a flamm

Request a quote

Description

Foam Chamber is used in one of the most common application to protect vertical fixed roof (cone) liquid storage tanks, with or without internal floating roof with the low expansion foam system. The application of foam is on the basis that the risk comprises the total surface area of the fuel.

The foam system design guidelines generally used are in accordance with NFPA-11, standard. Foam chambers are defined by NFPA-11 as Type II discharge outlets for delivering the foam to the surface of a flammable liquid. The Foam Chambers are widely used with the In-line Foam Inductor, Balance Pressure Foam Proportioning system, Bladder Tank Proportioner or Foam Tender.

Foam Chamber is an air aspirating foam discharge device, covering wide range of flow from 40 GPM to 1086 GPM at 40 to 100 psi inlet pressure. The Foam Chamber contains a Vapor seal to prevent the entry of Vapor into the foam chamber and the foam solution pipe. Each foam chamber is supplied with an orifice plate, designed for the required flow and inlet pressure.

Features

  • UL Listed/FM Approved
  • Heavy duty welded construction with choice of Carbon Steel or Stainless Steel material
  • Frangible Glass Vapor Seal
  • Controlled Air Flow proportional to liquid flow for optimum foam quality and rupture of Vapor seal in narrow pressure tolerances for increased reliability
  • Field replaceable orifice plate fitted with Foam Chamber

Specifications

Foam Concentrate Approval Working Pressure, psi NF-FC65 /

NF-FCSS65

NF-FC80 /

NF-FCSS80

NF-FC100 /

NF -FCSS100

NF-FCR150/

NF-FCRSS150

AFFF 3% UL 40-100 39.62-145.30 79.25-269.72 158.50-634.01 —
AR-AFFF 3/3 UL 40-100 39.62-145.30 79.25-269.72 158.50-634.01 —
AFFF 3% FM 40-100 for 65NB 50- 100 for other sizes 52-156 101-309 198-679 493-1048
AFFF 6% FM 50-100 59-158 94-303 195-674 489-1042
AR-AFFF 3/3 FM 50-100 57-167 110-311 211-678 516-1086
AR-AFFF 3/6 3% FM 50-100 59-157 107-305 197-675 512-1073
AR-AFFF 3/6 6% FM 50-100 59-157 100-304 192-680 514-1072

Catalogue family reference SHIELD-F-7966 identifies this manufacturer product page; it is not an orderable manufacturer SKU. Confirm the required model and configuration when requesting information.

Official manufacturer product information

Technical Specifications

AFFF 3%UL; 40-100; 39.62-145.30; 79.25-269.72; 158.50-634.01; —
AFFF 3% (2)FM; 40-100 for 65NB 50- 100 for other sizes; 52-156; 101-309; 198-679; 493-1048
AFFF 6%FM; 50-100; 59-158; 94-303; 195-674; 489-1042
AR-AFFF 3/3UL; 40-100; 39.62-145.30; 79.25-269.72; 158.50-634.01; —
AR-AFFF 3/3 (2)FM; 50-100; 57-167; 110-311; 211-678; 516-1086
AR-AFFF 3/6 3%FM; 50-100; 59-157; 107-305; 197-675; 512-1073
AR-AFFF 3/6 6%FM; 50-100; 59-157; 100-304; 192-680; 514-1072
Catalogue family referenceSHIELD-F-7966
Foam ConcentrateApproval; Working Pressure, psi; NF-FC65 / NF-FCSS65; NF-FC80 / NF-FCSS80; NF-FC100 / NF -FCSS100; NF-FCR150/ NF-FCRSS150
Published pressure statement 1Foam Chamber is an air aspirating foam discharge device, covering wide range of flow from 40 GPM to 1086 GPM at 40 to 100 psi inlet pressure. The Foam Chamber contains a Vapor seal to prevent the entry of Vapor into the foam chamber and the foam solution pipe. Each foam chamber is supplied with an orifice plate, designed for the required flow and inlet pressure.

Documents & Technical Downloads