
Fike MicroMist Water Mist System
Pre-engineered, self-contained water mist system supplied complete on a 70 or 112 US gallon skid, operating at 320 psig as an NFPA 750 intermediate-pressure system.
Request a quoteDescription
Pre-engineered, self-contained water mist system supplied complete on a 70 or 112 US gallon skid, operating at 320 psig as an NFPA 750 intermediate-pressure system.
- Function: Pre-engineered, self-contained water mist system
- Benefit: Pre-assembled with all necessary components to offer a simple-to-install water mist solution; particularly suited for applications where a water source is unavailable.
- Manufacturer listed standards and approvals: FM | NFPA 750 (intermediate pressure system)
How does a self-contained water mist system work?
When a fire condition is detected in the protected hazard, a releasing fire control panel sends a signal to the releasing module to operate the self-contained water mist suppression system (Micromist).
Nozzle design shears the water into small droplets, which are effective at producing water vapor when they make contact with the fire.
Valves on the nitrogen tanks open and the resulting air pressure flows through a pressure regulating valve (PRV) which regulates the pressure and drives the water through the opened water valve and to the system nozzles.
The water droplets absorb heat, oxygen is displaced by steam generation, and the cooling effect washes out combustion products, resulting in reliable fire extinguishment.
The Micromist system uses relatively short pulses of water to aid in the extinguishment of fires as well as minimize the property damage associated with a continuous discharge.
Catalogue reference identifies this product or system family. Individual configurations and ordering part numbers vary; consult the official documentation.
Technical Specifications
| Brand | Fike |
|---|---|
| Hazard classes | Flammable liquid Class B processes and incidental combustible Class A materials |
| Maximum ceiling height | 16 ft (4.9 m) |
| Maximum hazard volume | 9,175 ft3 (260 m3) |
| Operating pressure | 320 psig (22 bar), classified by NFPA 750 as an intermediate-pressure system |
| Protected hazard temperature | +40°F to +325°F (+4.4°C to +162.7°C) |
| Scope | Pre-engineered water storage, pipe and tube sizes, maximum and minimum pipe lengths, fittings and nozzles; acceptance by simple pressure-drop calculation |
| Skid ambient temperature | +40°F to +130°F (+4.4°C to +54.4°C); install outside the protected hazard area |
| Skid sizes | 70 gallon (265 litre) and 112 gallon (424 litre) skids |
| System type | Pre-engineered, self-contained, single-fluid water mist system |


