Edwards SIGA-OSHD-IN Signature Optica Intelligent Multisensor Smoke and Heat Detector, 135F Fixed with Rate of Rise
Indicative Price
Excluding local taxes and shipping.
Edwards SIGA-OSHD-IN — Signature Optica intelligent detector combining an optical smoke sensor with a rate-of-rise heat sensor and a fixed temperature threshold.
Description
Edwards SIGA-OSHD-IN — Signature Optica intelligent detector combining an optical smoke sensor with a rate-of-rise heat sensor and a fixed temperature threshold.
It reads several optical sensors at dual wavelengths and multiple angles, filters the particle data digitally and compares the result against preprogrammed settings, which is how it separates smoke from cooking particulate. The heat element is a second independent criterion, not a refinement of the smoke reading, and the detector works only with a Signature loop controller.
- Smoke sensitivity 0.5 to 4.36 %/ft., listed to UL 268 7th edition
- Heat at 15 °F per minute rate of rise with a 135 °F fixed point
- 15.20 to 19.95 VDC, 32 µA standby and 45 µA in alarm
- Listed heat spacing 50 ft. centres; air velocity to 4,000 ft./min
- Operating environment 32 to 100 °F
- Listed CAN/ULC-S529 and S530, UL 268-7, UL 268A, UL 521, CSFM, FM
SIGA-OSD is the smoke-only Optica detector: no heat element, no UL 521 or S530, and a wider 32 to 120 °F ambient. SIGA-OSHD-NL drops the visible logo and SIGA-OSHDB is black. Bases are ordered separately. No Edwards document read defines the –IN suffix; the Ordering block lists SIGA-OSHD, –NL and –B only.
Related Products
View Cataloguearrow_forward
Advanced AXIS-OHX Axis EN Multi-Sensor Detector W Isolator
Indicative Price
from

Advanced AXIS-OH Axis EN Multi-sensor Detector
Indicative Price
from

Cooper FXN922 Conventional Multi-Mode Detector
Indicative Price
from

Mircom MIX-2351TAP (Smoke and Thermal Sensor)
Indicative Price
from