Edwards SIGA-HCD Signature Multisensor Heat and CO Detector, Addressable
Indicative Price
Excluding local taxes and shipping.
Edwards SIGA-HCD — Signature Series addressable detector pairing rate-of-rise and fixed temperature heat sensing with a CO sensor in one head.
Description
Edwards SIGA-HCD — Signature Series addressable detector pairing rate-of-rise and fixed temperature heat sensing with a CO sensor in one head.
It analyses the heat sensor independently of the CO sensor and decides whether to raise a fire alarm, a life safety CO alarm, or both. Readings are digitised on board and weighed against stored history, and compensation is automatic.
- Rate of rise 15 °F per minute with a 135 °F fixed sensor, alarm point 129 to 141 °F
- Listed spacing to 50 ft. centres; FM Fixed Special, Fixed/ROR Ultra-fast
- CO alarm at 70 ppm over 60 to 240 min., 150 ppm over 10 to 50, 400 ppm over 4 to 15
- 15.20 to 19.95 VDC; 51 µA normal, 68 µA in alarm; 250 Signature addresses per loop
- Listed to UL 521, UL 2075 and ULC-S530, and to the CO limits of UL 2034
- CO sensor life ten years, after which the panel reports end of life
A base is a separate catalogue number: SIGA-SB standard, SIGA-RB relay, SIGA-IB isolator, or the SIGA-AB4GT and SIGA-AB4G-LF sounder bases, which need a SIGA-TCDR generator for CO mode. The SIGA-COD is CO only, with no heat sensor.
Related Products
View Cataloguearrow_forward
Advanced AXIS-OHX Axis EN Multi-Sensor Detector W Isolator
Indicative Price
from

Advanced AXIS-OH Axis EN Multi-sensor Detector
Indicative Price
from

Cooper FXN922 Conventional Multi-Mode Detector
Indicative Price
from

Mircom MIX-2351TAP (Smoke and Thermal Sensor)
Indicative Price
from