Edwards 721UT 700 Series Photoelectric Smoke Detector Head with Fixed and Rate-of-Rise Heat, Two-Wire, Remote LED Output
Indicative Price
Excluding local taxes and shipping.
Edwards 721UT — 700 Series two-wire photoelectric smoke detector head with integral fixed-temperature and rate-of-rise heat detection and remote LED output.
Description
Edwards 721UT — 700 Series two-wire photoelectric smoke detector head with integral fixed-temperature and rate-of-rise heat detection and remote LED output.
The 700 Series is self-diagnostic: if the detector drifts out of its listed sensitivity range the alarm LED flashes once a second, meeting NFPA 72 field sensitivity testing without an external meter. Head only; Edwards sells bases separately.
- Heat sensor fixed at 135 °F, plus rate of rise of 15 °F/min above 105 °F
- Remote alarm and trouble LED outputs, 5 to 8.5 mA; remote test input 100 Ω max
- 8.5 to 33 VDC, not polarity sensitive; alarm current up to 60 mA if not limited by the panel
- UL two-wire compatibility identifier S10A; series listed to UL 268
- Field-replaceable optical chamber and automatic drift compensation
- Head 4 in. diameter × 1.75 in. high
Not the 721U, which has the remote test and LED outputs but no heat sensor, nor the plain 711U head. The 721UT needs a six-terminal base such as the 702U; the three-terminal 701U is listed for the 711U and 713-5U heads only.
Availability note: The supplier lists this product as discontinued/legacy. Availability is limited and should be confirmed before ordering.
Related Products
View Cataloguearrow_forward
Advanced AXIS-OHX Axis EN Multi-Sensor Detector W Isolator
Indicative Price
from

Advanced AXIS-OH Axis EN Multi-sensor Detector
Indicative Price
from

Cooper FXN922 Conventional Multi-Mode Detector
Indicative Price
from

Mircom MIX-2351TAP (Smoke and Thermal Sensor)
Indicative Price
from