Eaton Zone monitor unit for addressable fire systems
Zone Monitors

Eaton Zone monitor unit for addressable fire systems

Eaton·SKU: EATON-F-991926D85EE4

Eaton's zone monitor unit enables the connection of a zone of Eaton conventional detectors and a separate zone of Eaton conventional callpoints (if required) to an Eaton addressable fire system. This interface allows for a wide variety of installations to be simplified without the use of specialist

Request a quote

Description

Eaton's zone monitor unit enables the connection of a zone of Eaton conventional detectors and a separate zone of Eaton conventional callpoints (if required) to an Eaton addressable fire system. This interface allows for a wide variety of installations to be simplified without the use of specialist or customised equipment, and allows for easier connection to existing conventional detection zones, as long as the devices used are compatible. An extensive range of interfaces are available to support the Eaton range of control panels, providing solutions for most design requirements.

Highlights

  • Simple installation: Plug and play
  • Flexible design: Surface or semi recessed mounted
  • Certification: EN54 approved

Pushing the limits with no maximum number of call points per zone

This interface was to designed to ease the process of expanding a system of up to 20 Eaton conventional detectors using existing wiring, saving on time and installation costs. No hard addressing is required making installation even more simple. The unit monitors inputs for open, short circuit and contact faults and allows an unlimited number of conventional call points per zone.

Product family: specifications and ordering options vary by model. Refer to the model details and official documentation.

Official Eaton product page

Technical Specifications

Alarm Current8mA
Callpoint LoadUnlimited
ConstructionPC / ABS
Current with 20 Detectors3.4mA
Detector Load20 detectors per zone (max)
Dimensions (HxWxD)88mm x 147mm x 60mm
Humidity (Non-condensing)0 to 95% RH
Ingress ProtectionIP40
Manufacturer highlight: CertificationEN54 approved
Manufacturer highlight: Flexible designSurface or semi recessed mounted
Manufacturer highlight: Simple installationPlug and play
Operating Temperature-10°C to +60°C
Operating Voltage18Vdc to 30Vdc
Quiescent Current2.8mA
StandardsEN54 Pt17 & Pt18 2005
Suitable for use withEaton addressable fire alarm systems
Weight0.23kg
Zone Monitor UnitCZMU352
Zone Monitor Unit - intrinsically safeCZMU352-IS

Documents & Technical Downloads