System Sensor 2W-B Photoelectric i3 Smoke Detector, 2-Wire
Indicative Price
Excluding local taxes and shipping.
Overview The System Sensor 2W-B is a two-wire photoelectric smoke detector from the i3 Series . The design ensures reliable fire detection in open areas. You can use it in commercial, residential, and light-industrial settings. The detector uses light-scattering photoelectric sensing. It has a sensi
Description
Overview
The System Sensor 2W-B is a two-wire photoelectric smoke detector from the i3 Series. The design ensures reliable fire detection in open areas. You can use it in commercial, residential, and light-industrial settings. The detector uses light-scattering photoelectric sensing. It has a sensitivity of 2.5% per foot of obscuration. You can plug it into a pre-wired base without difficulty. The Stop-Drop 'N Lock method allows for quick installation and removal during service.
Technical Details
The 2W-B runs on a 12/24 VDC non-polarized circuit. It needs at least 8.5V and can handle up to 35V. In standby, it draws 50 µA. During an alarm, it uses up to 130 mA, controlled by the panel. Drift compensation and smoothing algorithms adjust for dust in the sensing chamber. This helps reduce false alarms between service intervals. The unit is UL 268 listed for Fire Protective Signaling Systems. It also has more listings from FM, MEA, MSFM, and cETLus agencies.
Installation & Application
The detector's base fits on 3.5-inch and 4-inch octagonal, single-gang, and 4-inch square backboxes with a plaster ring. It can also mount directly to the ceiling with drywall anchors. Wiring terminates via SEMS screws accepting 14-22 AWG wire through a large entry port. The 2W-B works with the 2W-MOD2 loop test module or an i3-compatible panel. This setup allows remote maintenance signaling and the EZ Walk loop test. Technicians can check the loop wiring from the panel, eliminating the need to test each detector individually.
Comparative Positioning
Within the i3 Series lineup, the 2W-B serves as the base two-wire photoelectric model. Facilities needing fixed-temperature heat detection can upgrade to the 2WT-B. It has a 135°F thermal sensor and a 41°F freeze-trouble indicator. For four-wire circuits, you can use the 4W-B and 4WT-B models.
UPC: 783863017599
Also known as: BK-2WB, 2WB
Technical Specifications:
|
- Simplified sensitivity measurement
- Large wire entry port
- Built-in test switch
- Plug-in detector line, mounting base included
- Loop testing via EZ Walk feature
- Wide-angle, dual-color LED indication
- In-line terminals with SEMS screws
- Mounts to octagonal and single-gang back boxes, 4-square back boxes, or direct to ceiling
- Stop-Drop ’N Lock attachment to base
- Removable detector cover and chamber
- Built-in remote maintenance signaling
- Drift compensation and smoothing algorithms
Technical Specifications
| Alarm Current | 130mA max., limited by panel |
|---|---|
| Brand | System Sensor |
| Dimensions | 2.0" (51mm) H x 5.3" (127mm) Dia. |
| Manufacturer Part Number | 2W-B |
| Maximum Ripple Voltage | 30% of nominal (peak to peak) |
| Operating Humidity Range | 0% to 95% RH, noncondensing |
| Operating Temperature Range | 32° to 120°F (0° to 49°C) |
| Operating Voltage | 12/24 V non-polarized nominal, 8.5 min. to 35 max. |
| Sensitivity | 2.5%/ft. nominal |
| Smoke Detection Type | Photoelectric |
| Standby Current | 50 µA max. avg., 100 µA peak |
| UPC | 783863017599 |
| Weight | 6.3 oz. (178 g) |
| Wiring | 2-wire |
| Wiring Gauge | 14-22 AWG |
Documents & Technical Downloads