Shield VERTICAL SIDEWALL SPRINKLER
MODEL: SD2133, SD2121 The SD2133, SD2121, ½” orifice, standard vertical sidewall sprinkler is designed for standard installation. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (standard or quick response) for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast wit
Request a quoteDescription
MODEL: SD2133, SD2121
The SD2133, SD2121, ½” orifice, standard vertical sidewall sprinkler is designed for standard installation. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (standard or quick response) for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames.
It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings and finishes to meet many design requirements. The recessed pendent should be utilized with a recessed escutcheon which provides up .” of adjustments. All sprinklers are manufactured using the time proven Belleville seal used exclusively by all major manufactures to ensure long life and safe operation.
Features
MODEL: SD2133, SD2121
The SD2133, SD2121, ½” orifice, standard vertical sidewall sprinkler is designed for standard installation. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (standard or quick response) for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames.
It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings and finishes to meet many design requirements. The recessed pendent should be utilized with a recessed escutcheon which provides up .” of adjustments. All sprinklers are manufactured using the time proven Belleville seal used exclusively by all major manufactures to ensure long life and safe operation.
Specifications
| SPRINKLER IDENTIFICATION NUMBER | Standard SD2133 (bulb 5mm), Quick Response SD2121 (bulb 3mm) |
|---|---|
| STYLE | Vertical Sidewall |
| FINISH | Natural/Chrome |
| K FACTOR | 5.6gpm/psi½. (80lpm/bar½) |
| RESPONSE TIME INDEX (RTI) | Standard 50 (m.s)½ Quick Response 30 (m.s)½ |
| NOMINAL THREAD SIZE | ½”NPT(15mm) |
| ORIFICE SIZE | 13mm |
| MAX. WORKING PRESSURE | 175PSI(1200kPa) |
| FACTORY HYDROSTATIC TEST | 100%@500PSI(3450 kPa) |
| MIN. OPERATION PRESSURE | 7 PSI(48 kPa) |
Catalogue family reference SHIELD-F-6532 identifies this manufacturer product page; it is not an orderable manufacturer SKU. Confirm the required model and configuration when requesting information.
Technical Specifications
| Catalogue family reference | SHIELD-F-6532 |
|---|