Fire Protection Valves
Shield POST INDICATORS
Shield·SKU: SHIELD-F-7095
Vertical Indicator Post SD-800GO INDICATOR POST – SD-800
Request a quoteDescription
- Vertical Indicator Post
- SD-800GO
- INDICATOR POST – SD-800
Features
- Meet or exceed the requirements of NFPA 24 standard.
- Indicates the state of the valve OPEN or SHUT position.
- Target nut to allow 13 to 51 turns for F0600-IP.
- “L” shaped wrench handle fitted with a secure padlock (provided by user).
- Protected windows.
- Easily adjustable indicator OPEN and SHUT targets.
- UL/ULC 789 listed and FM 1110 approved.
Specifications
Vertical Indicator Post
- Fusion bonded coating interior and exterior.
- Tapped supervisory tamper switch.
- Operating nut: Bronze ASTM B584 C8440/B62 C83600
- Operating Carrier Nut: Bronze ASTM B584 C84400/B62 C83600
- Stainless Steel Fasteners: A2-70 OR A4-70
SD-800GO
- Adjustable type vertical mounted
- Sizes : 14” to 24”
- Post Indicator Body : Cast Iron ASTM A126 Class B
- Vertical type enables underground fire line valves to be operated at ground level with operating wrench.
- Built In gear drive.
- 2:1 gear ratio to reduce valve operating torque.
- Enclosed and completely sealed to provide the ultimate in corrosion protection.
INDICATOR POST
- Resilient Seated Gate Valves are in accordance with ANSI /AWWA C515 Standard.
- Body, bonnet, and wedge of the gate valve shall be of high strength Ductile Iron, ASTM A536, Grade 65-45-12.
- Valves Fusion Bonded Epoxy Coated Interior and Exterior, ANSI / AWWA C550.
- Stuffing Box Gland shall have a minimum of three (3) O-rings capable of replacement under pressure while gate is in the full open position.
- EPDM O-ring Seals shall be located between Stuffing Box Gland, Bonnet, and Body.
- Operating Stem shall be 431 Stainless Steel with (3) Machined Grooves located just above the Lower Stem O-ring to accept and mate with a 2-piece Brass Split Ring. The design of the Stem and Split Ring will eliminate any upward or downward operating thrust on any Iron service.
- Underwriters Laboratories Listed with a Pressure Rating of 250 psi for 14″, 16″, 18″ sizes, and 200 psi for 20″, 24″ sizes.
INDICATOR POST – FIELD ADJUSTMENT
- Remove the top section from the top of the Indicator Post assembly.
- Cut the required stem length and adjust the Standpipe to match the ground line.
- Set the “OPEN” and “SHUT” targets for the appropriate valve size.
- Reattach the top section to the top of the Indicator Post assembly.
- Design and material are subject to change without notice.
INDICATOR POST – SD-800
- Adjustable type vertical mounted
- Vertical type enables underground fire line valves to be operated at ground level with operating wrench
- Compactable to be used with supervisory switches
Catalogue family reference SHIELD-F-7095 identifies this manufacturer product page; it is not an orderable manufacturer SKU. Confirm the required model and configuration when requesting information.
Technical Specifications
| Catalogue family reference | SHIELD-F-7095 |
|---|---|
| Operating Carrier Nut | Bronze ASTM B584 C84400/B62 C83600 |
| Operating nut | Bronze ASTM B584 C8440/B62 C83600 |
| Post Indicator Body | Cast Iron ASTM A126 Class B |
| Published manufacturer stated standards statement 1 | Meet or exceed the requirements of NFPA 24 standard. |
| Published pressure statement 1 | Underwriters Laboratories Listed with a Pressure Rating of 250 psi for 14″, 16″, 18″ sizes, and 200 psi for 20″, 24″ sizes. |
| Sizes | 14” to 24” |
| Stainless Steel Fasteners | A2-70 OR A4-70 |