Shield HORIZONTAL SIDEWALL SPRINKLER, QUICK RESPONSE, EXTENDED COVERAGE
Sprinkler Systems

Shield HORIZONTAL SIDEWALL SPRINKLER, QUICK RESPONSE, EXTENDED COVERAGE

Shield·SKU: SD8220

MODEL: SD8220 The Model SD8220, ¾” orifice, Extended Coverage Horizontal sidewall sprinkler is designed for extended coverage or recessed installation. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (quick response) for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames. It i

Request a quote

Description

MODEL: SD8220

The Model SD8220, ¾” orifice, Extended Coverage Horizontal sidewall sprinkler is designed for extended coverage or recessed installation. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (quick response) for prompt, precise operation. The die cast frame is more
streamlined and attractive than traditional sand cast frames.

It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings (see chart on page 2) and finishes to meet many design requirements. The recessed pendent should be utilized with a recessed escutcheon which provides up ¾” of adjustments.

 

Features

OPERATION

The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire, the ambient temperature rises causing the liquid in the bulb to expand.

When the ambient temperature reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the waterway is cleared of all sealing parts and water is discharged towards the deflector. The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire.

MAXIMUM COVERAGE

Standard spray coverage is up to: Light Hazard = 384sq.ft.
(35.8m2); Ordinary Hazard = 256sq.ft. (24m2) per NFPA 13.

Specifications

SPRINKLER IDENTIFICATION
NUMBER
Quick Response, Extended
Coverage SD8220 (bulb 3mm)
STYLE Horizontal Sidewall
K FACTOR 8.0 Imp. (114S.I)
RESPONSE TIME INDEX (RTI) < 33 (m/s1/2) Quick Response
NOMINAL THREAD SIZE ¾” NPT (20 mm)
MAX. WORKING PRESSURE 175 PSI (1200 kPa)
FACTORY HYDROSTATIC TEST 100 % @500 PSI(3450 kPa)
MIN. OPERATION PRESSURE 7 PSI (48 kPa)
RATINGS
SPRINKLER TEMPERATURE
CLASSIFICATION
NOMINAL SPRINKLER
TEMPERATURE RATING
N.F.P.A. MAXIMUM AMBIENT
(CEILING) TEMP. (ALLOWED)
GLASS BULB
COLOR
Ordinary 135℉/57℃ 100℉/38℃ Orange
Ordinary 155℉/68℃ 100℉/38℃ Red
Intermediate 175℉/79℃ 150℉/65℃ Yellow
Intermediate 200℉/93℃ 150℉/65℃ Green

Official manufacturer product information

Technical Specifications

IntermediateNOMINAL SPRINKLER TEMPERATURE RATING: 175℉/79℃; N.F.P.A. MAXIMUM AMBIENT (CEILING) TEMP. (ALLOWED): 150℉/65℃; GLASS BULB COLOR: Yellow
Intermediate (2)NOMINAL SPRINKLER TEMPERATURE RATING: 200℉/93℃; N.F.P.A. MAXIMUM AMBIENT (CEILING) TEMP. (ALLOWED): 150℉/65℃; GLASS BULB COLOR: Green
Manufacturer modelSD8220
OrdinaryNOMINAL SPRINKLER TEMPERATURE RATING: 135℉/57℃; N.F.P.A. MAXIMUM AMBIENT (CEILING) TEMP. (ALLOWED): 100℉/38℃; GLASS BULB COLOR: Orange
Ordinary (2)NOMINAL SPRINKLER TEMPERATURE RATING: 155℉/68℃; N.F.P.A. MAXIMUM AMBIENT (CEILING) TEMP. (ALLOWED): 100℉/38℃; GLASS BULB COLOR: Red
Published manufacturer stated standards statement 1Standard spray coverage is up to: Light Hazard = 384sq.ft. (35.8m2); Ordinary Hazard = 256sq.ft. (24m2) per NFPA 13.

Documents & Technical Downloads