Shield DIGITAL LHD CONTROL MODULE
Shield Digital LHD Control Module (LH-DCM) is designed to enhance the functionality of existing or new Digital LHD systems. The Module is intended to be installed between the Digital LHD cable and a conventional or addressable re alarm control panel. The LH-DCM simultaneously monitors two zones of Digital LHD cable (up to 3,000 metres per zone) for an alarm or fault condition. If an overheat or fire situation triggers either zone of the Digital LHD cable, the LH-DCM automatically calculates and
Request a quoteDescription
Shield Digital LHD Control Module (LH-DCM) is designed to enhance the functionality of existing or new Digital LHD systems. The Module is intended to be installed between the Digital LHD cable and a conventional or addressable re alarm control panel.
The LH-DCM simultaneously monitors two zones of Digital LHD cable (up to 3,000 metres per zone) for an alarm or fault condition. If an overheat or fire situation triggers either zone of the Digital LHD cable, the LH-DCM automatically calculates and displays the distance along the cable, in feet and metres, to the alarm point. The two zones can operate independently of each other or in interlock/coincidence detection mode to eliminate the possibility of false alarms.
An RS-485 Modbus RTU output also allows direct connection into a PLC or other process control system.
Features
- Advanced functionality for traditional Digital LHD systems.
- Pinpoints exact location of an incident and responds immediately.
- Simultaneous monitoring of up to two zones.
- Power indicator, fault and alarm lights for each zone.
- Volt-free outputs for fault and alarm, corresponding to each zone.
- Can be connected to an industrial process control system using the two-wire RS485 Modbus RTU output.
- Built-in sounder for audible annunciation.
- Interlock/Coincidence detection eliminates the possibility of false alarms by requiring both LHD cables to trigger before transmitting an alarm.
Specifications
| INPUTS* | |
|---|---|
| Max zone length | 3000m |
| Min zone length | 1m |
| End of line resistor | 1k ohm (Included) |
| Short circuit current | 0.5mA |
| Max voltage | 5V |
| Ground fault impedence | 0 ohms |
| OUTPUTS | |
| Communications | 2 wire RS-485 Modbus RTU/ASCII |
| Sounder | 2.4kHz 92dBa@10cm Buzzer |
| Alarm | volt-free relay contacts |
| Max voltage | 30Vac or 42.4Vdc |
| Max current | 2A |
| Max switching power | 60W, 62.SV |
| Fault | 2 x optoisolated phototransistor output |
| Max voltage | 35Vdc |
| Max current | 80mA |
| Max power dissipation | 150mW |
| * Upto two Class B zones of Shield Digital LHD Cable | |
| ** All circuit power limited if powered fom a power limited supply. | |
| MECHANICAL | |
| Dimensions (HxWxD) | 180 x 120 x 60.5 mm |
| Rating | NEMA 4, 4X (IP65) |
| Finish | Light Gray with clear lid |
| Display | 2 line, 16 character backlit display showing zone status |
| Terminal block spacing | 5mm Rising Clamp |
| Terminal block wire size | 0.08mm² (28AWG) to 4mm² (11AWG) |
| ELECTRICAL** | |
| Operating voltage (UL Tested) | 14Vdc Min / 24Vdc |
| Operating voltage | 12Vdc Min / 24Vdc Nominal / 36Vdc Max |
| Current cons. (Standby) | <15mA Min / <7mA Nominal / <5mA Max |
| Current cons. (Alarm) | <40mA Min / <23mA Nominal / <15mA Max |
| Terminal block rating | 16A |
| Supervised circuits | Power, Input Zone 1 & Input Zone 2 |
| ENVIRONMENTAL | |
| Operating Temperature | -20°C to +50°C |
Catalogue family reference SHIELD-F-7077 identifies this manufacturer product page; it is not an orderable manufacturer SKU. Confirm the required model and configuration when requesting information.
Technical Specifications
| Alarm | volt-free relay contacts |
|---|---|
| Catalogue family reference | SHIELD-F-7077 |
| Communications | 2 wire RS-485 Modbus RTU/ASCII |
| Current cons. (Alarm) | <40mA Min / <23mA Nominal / <15mA Max |
| Current cons. (Standby) | <15mA Min / <7mA Nominal / <5mA Max |
| Dimensions (HxWxD) | 180 x 120 x 60.5 mm |
| Display | 2 line, 16 character backlit display showing zone status |
| End of line resistor | 1k ohm (Included) |
| Fault | 2 x optoisolated phototransistor output |
| Finish | Light Gray with clear lid |
| Ground fault impedence | 0 ohms |
| Max current | 2A |
| Max current (2) | 80mA |
| Max power dissipation | 150mW |
| Max switching power | 60W, 62.SV |
| Max voltage | 5V |
| Max voltage (2) | 30Vac or 42.4Vdc |
| Max voltage (3) | 35Vdc |
| Max zone length | 3000m |
| Min zone length | 1m |
| Operating Temperature | -20°C to +50°C |
| Operating voltage | 12Vdc Min / 24Vdc Nominal / 36Vdc Max |
| Operating voltage (UL Tested) | 14Vdc Min / 24Vdc |
| Rating | NEMA 4, 4X (IP65) |
| Short circuit current | 0.5mA |
| Sounder | 2.4kHz 92dBa@10cm Buzzer |
| Supervised circuits | Power, Input Zone 1 & Input Zone 2 |
| Terminal block rating | 16A |
| Terminal block spacing | 5mm Rising Clamp |
| Terminal block wire size | 0.08mm² (28AWG) to 4mm² (11AWG) |