Shield 120V AC Input Output Module
Interface Modules

Shield 120V AC Input Output Module

Shield·SKU: SHIELD-F-6864

SHIELD 120V AC Input/Output Module is a loop powered device which incorporates a monitored input circuit for connection to dry contacts, as well as a 4A rated dry contact relay output. It is mounted in a plastic facia plate for use with a 4″ square or 2 gang electrical back box.

Request a quote

Description

SHIELD 120V AC Input/Output Module is a loop powered device which incorporates a monitored input circuit for connection to dry contacts, as well as a 4A rated dry contact relay output. It is mounted in a plastic facia plate for use with a 4″ square or 2 gang electrical back box.

Features

  • Loop-powered
  • Visible LEDs
  • 4A rated dry contact

Specifications

SPECIFICATION
TYPE 120 V AC Input/Output Module
STYLE Fascia Plate With Wiring Terminals
TEMPERATURE RANGE 0°C to 49°C
WIRING SIZE 24 AWG – 14 AWG
SIGNAL LINE CIRCUIT (SLC) Supervised Power Limited
OPERATING VOLTAGE 17 – 28 V DC
20-28 V DC (UL listed)
MODULATION VOLTAGE 5 – 9 V DC (peak to peak)
OPERATING CURRENT Supervisory Current at 17 V <0.95 mA
Alarm Current at 17 V <2.80 mA
Supervisory Current at 28 V <0.95 mA
Alarm Current at 28 V <3 mA (LED on)
Maximum Alarm Current <5 mA
FUNCTIONAL STATES Analog Level (normal) 16
Analog Level (alarm) 64
Analog Level (trouble) 4
DIMENSIONS (L X W X D) 114 mm x 114 mm x 25 mm

Catalogue family reference SHIELD-F-6864 identifies this manufacturer product page; it is not an orderable manufacturer SKU. Confirm the required model and configuration when requesting information.

Official manufacturer product information

Technical Specifications

Alarm Current at 17 V<2.80 mA
Alarm Current at 28 V<3 mA (LED on)
Analog Level (alarm)64
Analog Level (trouble)4
Catalogue family referenceSHIELD-F-6864
Maximum Alarm Current<5 mA
Published operating voltage statement 1SHIELD 120V AC Input/Output Module is a loop powered device which incorporates a monitored input circuit for connection to dry contacts, as well as a 4A rated dry contact relay output. It is mounted in a plastic facia plate for use with a 4″ square or 2 gang electrical back box.
Supervisory Current at 28 V<0.95 mA