Sigma XT Extinguishant Control Panel
Extinguishant Control Panels

Sigma XT Extinguishant Control Panel

protec·SKU: SIGMA XT/S

Three detection zones as standard; Configurable detection delays; Compatible with I.S barriers; Configurable first stage sounder delays; Zero time delay upon manual release option; Countdown timer shows time remaining until release; Supports up to seven, four wire status indicators; Built in...

Request a quote

Description

Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the extinguishant releasing panel offers outstanding value and performance for all small and medium fixed firefighting installations.

With three detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications.

The extensive configuration options of the panel allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-01)

The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety. The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status.

With all of the electronics mounted on a single, easily removable, steel plate panels are both robust and easy to install.

For compatible status units click here

Programmable Functions

  • Access Level 2
  • Test Zones 1 to 3
  • Disable Zones 1 to 3
  • Disable 1st Stage Alarms
  • Disable Pre-activated 1st Stage Relay
  • Disable Pre-activated 2nd Stage Relay
  • Disable Extract Fan Output
  • Disable Manual Release Input
  • Disable Extinguishant Sub System
  • Activate Extract Fan Output
  • Activate Alarm Delays

Access Level 3

  • Sounder Delay
  • Coincidence Detection
  • Disable Panel Features
  • Zone Alarm Delays (Detectors)
  • Zone Alarm Delay (Call Points)
  • Configure Zone for I.S Barrier Use
  • Zone Short Circuit Alarm
  • Zone Non Latching
  • Zone Inputs Delay
  • Extinguishant Release Time Delay
  • Extinguishant Release Duration Timer
  • Extinguishant Reset Delay Timer

Part Codes

Note: Special finish flushing collars for surface enclosures are available on request

Official Protec product information

Technical Specifications

Battery charge current0.7A maximum
Battery charge voltage27.6VDC nominal (temperature compensated)
Battery fuse20mm, 3.15A glass
Battery type (Yuasa NP)Two 12 Volt 7Ah sealed lead acid in series
BrandProtec
CablingFP200 or equivalent
Call point alarm threshold399 ohms to 100 ohms
Colour – controls plate & lablesRAL 7047 light grey – satin
Colour – lid & boxBS 00 A 05 grey – fine texture
Construction1.2mm mild sheet steel
Detection circuit end of line6K8 5% ½ Watt resistor
Detector alarm threshold999 ohms to 400 ohms
Dimensions (mm)385(W) x 310(H) x 90(D)
Extinguishant output EOL1N4004 Diode
Extinguishant release delayAdjustable 0 to 60 seconds (in 5 second steps)
Extinguishant release durationAdjustable 60 to 300 seconds (in 5 second steps)
Extinguishant release outputFused at 1 Amp
Extract contact rating30VDC 1A Amp maximum
Fault relay contact rating30VDC 1A Amp maximum
FinishEpoxy powder coated
fire relay contact rating30VDC 1A Amp maximum
First stage contact rating30VDC 1A Amp maximum
Head removal condition15.5 to 17.5 volts
IP RatingIP30
Local fire relay contact rating30VDC 1A Amp maximum
Mains supply230V AC + 10%/-15% (100 Watts maximum)
Mains supply fuse1.6 Amp (F1.6A L250V)
Maximum current draw from batteries3 Amps
Maximum ripple current200 millivolts
Monitored input end of line6K8 5% ½ Watt resistor
Monitored inputs alarm threshold999 ohms to 100 ohms
Monitored inputs normal threshold8K ohms to 1K ohm
Monitored inputs Short circuit threshold99 ohms to 0 ohms
No. of detection circuits3
No. of sounder circuits2 x 1st Stage, 1 x 2nd Stage
Number of detectors per zoneDependent on type (maximum 32)
Number of sounders per circuitDependent on type (max. 0.5A per sounder circuit)
Power supply rating3 Amps total including battery charge 28V +/- 2V
Quiescent current of panel in mains fail0.095A
R0V outputFused at 500mA with electronic fuse
Second stage contact rating30VDC 1A Amp maximum
Short circuit threshold99 ohms to 0 ohms
SIL, AL, FLT, RST inputsSwitched -ve, max resistance 100 Ohms
Sounder circuit end of line10K 5% ¼ Watt resistor
Sounder outputs24V Fused at 500mA with electronic fure
Status unit power outputFused at 500mA with electronic fuse
Status unit/Ancillary board connectionTwo wire RS485 connection
Terminal capacity0.5mm² to 2.5mm² solid or standed wire
Weight6kg
Zone normal threshold8K ohms to 1K ohm
Zone quiescent current2mA maximum