Sigma XT Extinguishant Control Panel
Three detection zones as standard; Configurable detection delays; Compatible with I.S barriers; Configurable first stage sounder delays; Zero time delay upon manual release option; Countdown timer shows time remaining until release; Supports up to seven, four wire status indicators; Built in...
Request a quoteDescription
Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the extinguishant releasing panel offers outstanding value and performance for all small and medium fixed firefighting installations.
With three detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications.
The extensive configuration options of the panel allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-01)
The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety. The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status.
With all of the electronics mounted on a single, easily removable, steel plate panels are both robust and easy to install.
For compatible status units click here
Programmable Functions
- Access Level 2
- Test Zones 1 to 3
- Disable Zones 1 to 3
- Disable 1st Stage Alarms
- Disable Pre-activated 1st Stage Relay
- Disable Pre-activated 2nd Stage Relay
- Disable Extract Fan Output
- Disable Manual Release Input
- Disable Extinguishant Sub System
- Activate Extract Fan Output
- Activate Alarm Delays
Access Level 3
- Sounder Delay
- Coincidence Detection
- Disable Panel Features
- Zone Alarm Delays (Detectors)
- Zone Alarm Delay (Call Points)
- Configure Zone for I.S Barrier Use
- Zone Short Circuit Alarm
- Zone Non Latching
- Zone Inputs Delay
- Extinguishant Release Time Delay
- Extinguishant Release Duration Timer
- Extinguishant Reset Delay Timer
Part Codes
Note: Special finish flushing collars for surface enclosures are available on request
Technical Specifications
| Battery charge current | 0.7A maximum |
|---|---|
| Battery charge voltage | 27.6VDC nominal (temperature compensated) |
| Battery fuse | 20mm, 3.15A glass |
| Battery type (Yuasa NP) | Two 12 Volt 7Ah sealed lead acid in series |
| Brand | Protec |
| Cabling | FP200 or equivalent |
| Call point alarm threshold | 399 ohms to 100 ohms |
| Colour – controls plate & lables | RAL 7047 light grey – satin |
| Colour – lid & box | BS 00 A 05 grey – fine texture |
| Construction | 1.2mm mild sheet steel |
| Detection circuit end of line | 6K8 5% ½ Watt resistor |
| Detector alarm threshold | 999 ohms to 400 ohms |
| Dimensions (mm) | 385(W) x 310(H) x 90(D) |
| Extinguishant output EOL | 1N4004 Diode |
| Extinguishant release delay | Adjustable 0 to 60 seconds (in 5 second steps) |
| Extinguishant release duration | Adjustable 60 to 300 seconds (in 5 second steps) |
| Extinguishant release output | Fused at 1 Amp |
| Extract contact rating | 30VDC 1A Amp maximum |
| Fault relay contact rating | 30VDC 1A Amp maximum |
| Finish | Epoxy powder coated |
| fire relay contact rating | 30VDC 1A Amp maximum |
| First stage contact rating | 30VDC 1A Amp maximum |
| Head removal condition | 15.5 to 17.5 volts |
| IP Rating | IP30 |
| Local fire relay contact rating | 30VDC 1A Amp maximum |
| Mains supply | 230V AC + 10%/-15% (100 Watts maximum) |
| Mains supply fuse | 1.6 Amp (F1.6A L250V) |
| Maximum current draw from batteries | 3 Amps |
| Maximum ripple current | 200 millivolts |
| Monitored input end of line | 6K8 5% ½ Watt resistor |
| Monitored inputs alarm threshold | 999 ohms to 100 ohms |
| Monitored inputs normal threshold | 8K ohms to 1K ohm |
| Monitored inputs Short circuit threshold | 99 ohms to 0 ohms |
| No. of detection circuits | 3 |
| No. of sounder circuits | 2 x 1st Stage, 1 x 2nd Stage |
| Number of detectors per zone | Dependent on type (maximum 32) |
| Number of sounders per circuit | Dependent on type (max. 0.5A per sounder circuit) |
| Power supply rating | 3 Amps total including battery charge 28V +/- 2V |
| Quiescent current of panel in mains fail | 0.095A |
| R0V output | Fused at 500mA with electronic fuse |
| Second stage contact rating | 30VDC 1A Amp maximum |
| Short circuit threshold | 99 ohms to 0 ohms |
| SIL, AL, FLT, RST inputs | Switched -ve, max resistance 100 Ohms |
| Sounder circuit end of line | 10K 5% ¼ Watt resistor |
| Sounder outputs | 24V Fused at 500mA with electronic fure |
| Status unit power output | Fused at 500mA with electronic fuse |
| Status unit/Ancillary board connection | Two wire RS485 connection |
| Terminal capacity | 0.5mm² to 2.5mm² solid or standed wire |
| Weight | 6kg |
| Zone normal threshold | 8K ohms to 1K ohm |
| Zone quiescent current | 2mA maximum |