Sigma XT+ 4 Multi Area Extinguishant Control Panel
Extinguishant Control Panels

Sigma XT+ 4 Multi Area Extinguishant Control Panel

protec·SKU: SIGMA-XT-4

2, 4 or 8 detection zones; 1 to 4 extinguishant areas; Dual extinguishant outputs for each area (configurable as Main/Reserve); First and second stage sounder outputs for each area; First and second stage volt free changeover contacts for each area; Released volt free contact per area; Fault...

Request a quote

Description

Sigma XT+ control panels are multi-area extinguishant control panels complying with EN12094-1, EN54-2 and EN54-4. Up to 8 zones of conventional detection with up to 4 extinguishant areas are available.

Stand alone extinguishant control units are also available with 2 monitored inputs to receive initiating signals from remote fire detection control panels or addressable modules.

Each extinguishant area has a comprehensive set of inputs and outputs and is configurable via a simple programming interface. All extinguishant areas may have up to 7, serially connected Sigma Si status indication and control units or ancillary relay boards connected via a simple 4 core cable.

The versatility of the control panel can be enhanced further by the fitting of up to 7 Sigma CP Ancillary boards (K580) or Sigma CP Sounder boards (K461) to the RS485 serial bus.

For compatible status units click here .

Key Features continued from above…

  • Extract fan control
  • Countdown indicator shows time until release in seconds
  • Mode select and manual release controls per area
  • Monitored remote manual release input
  • Monitored remote Hold input
  • Monitored remote Mode select (door interlock) input
  • Monitored remote Released pressure switch input
  • Monitored remote Low Pressure switch input
  • Monitored Abort input
  • Serial connection for Sigma Si status units and ancillary boards

Official Protec product information

Technical Specifications

1st and 2nd stage Sounder outputs21 to 28V DC Fused at 1A with electronic fuse
Battery charge current0.7A maximum
Battery charge voltage27.6VDC nominal (temperature compensated)
Battery fuse20mm, 3.15A glass
BrandProtec
CablingFP200 or equivalent (max capacitance 1uF max inductance 1 mH)
Call point alarm threshold370 ohms to 150 ohms
Colour – controls plate & lablesRAL 7047 light grey – sation
Colour – lid & boxBS 00 A 05 grey – fine texture
Construction1.2mm mild sheet steel
Current draw in mains fail condition54 milliamps per module
Detection circuit end of line6K8 +/- 5% ½ Watt resistor
Detector alarm threshold1K ohm to 390 ohms
Dimensions (mm)385(W) x 520(H) x 110(D) 385(W) x 700(H) x 145(D)
Extinguishant output end of line1N4004 Diode
Extinguishant release delayAdjustable 0 to 60 seconds (+/- 10%)
Extinguishant release durationAdjustable 60 to 300 seconds
Extinguishant release output21 to 28V DC. Fused at 1 Amp
Extract contact rating5 to 30VDC 1A Amp maximum for each
Fault relay contact rating5 to 30VDC 1A Amp maximum for each
FinishEpoxy powder coated
Fire relay contact rating5 to 30VDC 1A Amp maximum for each
Fire stage contact rating5 to 30VDC 1A Amp maximum for each
Head removal condition15.5 to 17.5 volts
IP RatingIP30
Local fire relay contact rating5 to 30VDC 1A Amp maximum for each
Mains supply230V AC, 50HZ + 10% – 15% (100 Watts maximum)
Mains supply fuse1.6 Amp (F1.6A L250V)
Max. current draw from betteries3A or 4A (Model dependant)
Maximum ripple current200 millivolts
Monitored input end of line6K8 +- 5% ½ Watt resistor
Monitored inputs alarm threshold2K ohms to 150 ohms +/- 5%
Monitored inputs normal threshold (Allowable EOL)10K ohm to 2K ohm
Monitored inputs Short circuit threshold140 ohms to 0 ohms +/- 5%
No. of detection circuitsTwo to eight. 21 to 28V DC
No. of sounder circuitsDependent on model 21 to 28V DC
Number of detectors per zoneDependent on type – typically 20
Number of sounders per circuitDependent on type and current consumption – typically 20+
Power supply rating (1 & 2 area units)3 Amps total including battery charge 28V +/- 2V
Power supply rating (3 & 4 area units)5.25 Amps including battery charge 28V +/- 2V
Second stage contact rating5 to 30VDC 1A Amp maximum for each
Short circuit threshold130 ohms to 0 ohms
Sigma CP Aux 24V outputFused at 2.5A – not available to user
Sigma XT+ module Aux 24V outputFused at 500mA with electronic fuse -1 per extinguishant area
SIL, AL, FLT, RST inputsSwitched -ve, min resistance 0ohms, max resistance 100 Ohms
Sounder circuit end of line10K +/- 5% ¼ Watt resistor
Status unit power output21 to 28V DC. Fused at 500mA with electronic fuse
Status unit/Ancillary board connectionTwo wired RS485 connection (EIA-485 specification)
Terminal capacity0.5mm² to 2.5mm² solid or stranded wire
Weight8kg (standard panel)
Zone normal threshold (Allowable EOL)10K ohm to 2K ohm
Zone quiescent current0mA minimum, 2mA maximum

Documents & Technical Downloads