ProPoint PLUS Aspirating Smoke Detectors
Smoke Detectors

ProPoint PLUS Aspirating Smoke Detectors

protec·SKU: PROPOINT-PLUS

1 – 4 Individual detectors per aspirator (providing up to 4 separately identifiable areas); High performance optical ‘Scatter Chamber Detectors’ (SCD); High performance optical ‘Scatter Chamber Detectors’ (SCD) and enhanced CO detection; Multiple language, multi-function LCD display; Simple...

Request a quote

Description

ProPoint PLUS Optical ‘Smoke’ and ‘Smoke/CO’ detection

Aspirating detection is now a recognised solution for many different fire detection applications. ProPoint PLUS provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator.

Each of the four plug-in ‘Scatter Chamber Detectors’ (SCD)’s detector modules can be either ‘optical’ only or combined ‘optical/enhanced CO’ detectors, the CO sensor is only suitable for small room applications. Independent and integrated alarm decision making through the use of complex algorithms extend the range of particle detection, confirm genuine alarms and reduce unwanted alarms.

Installation, configuration and commissioning of ProPoint PLUS detectors is very simple and installer friendly.

Configuration to either Class A, Class B or Class C sensitivity options is achieved through a multi-language, multi-function LCD display without the need for a laptop connection.

Detector set up allows the installer to configure the detector sensitivity to an equivalent setting, as a known number of point type smoke detectors for each Class A, Class B and Class C system. This ensures the system specifier, designer, installer and commissioning engineer configure the ProPoint PLUS SCD’s to the correct sensitivity for the particular application.

Aspirator fan speed and airflow configuration is a also a very simple process allowing ProPoint PLUS aspirating detectors to be installed in a variety of applications with short and relatively long pipe runs.

Official Protec product information

Technical Specifications

Airflow Monitoring‘High Airflow’ and ‘Low Airflow’ fault monitoring
Alarm IndicationsPre-alarm, Fire
Application Sampled Air Temperature-20˚C to 60˚C (-4˚F to 140˚F)
BrandProtec
Cable Access10 x 20mm knock outs
Cable TerminationScrew terminal blocks (0.2 – 2.5mm2, 30 – 12AWG)
Current Consumption @ 24VDC, 100% Fan 4 pipe580mA quiescent | 620mA alarm
Dimensions (mm)380(H) x 250(W) x 137(D)
Event Log / Data Retention24,000 events stored on FIFO basis (alarms, actions, faults and data points) (Approx 30 day historical graph data)
Fault ContactRated at 30VDC 1A maximum [Normally closed]
Humidity10 – 93%RH (no icing / non-condensing)
IP RatingIP30
Other IndicationsSupply Healthy, General Fault, OLED Display with four navigation buttons
Pipe Outer Diameter25mm, push to fit tapered inlet
Programmable Inputs3 monitored inputs that may be configured for Isolate, Reset, Silence, Battery Fault and Mains Fault
Programmable Output Contacts5 contacts rated 30VDC 1A [Volt-free change over contacts with 28 programming options]
Sampling Pipe NetworkNumber of inlet ports: Up to four Pipe Network Design Tool: ProFlow Maximum pipe length: Specific to individual design. To be compliant to local design codes, and verified by ProFlow.
Sensitivity RangeOptical Detection Range: 0.12%obs/m to 11%obs/m Carbon Monoxide Detection Range: 1 to 150 ppm
Standards / ApprovalsEN 54-17, EN 54-20 AS 7240-20 UKCA CE
Supply Voltage21 – 28VDC
Temperature Range Tested to EN54-20-10˚C to 55˚C (32˚F to 131˚F)
Threshold Settings Compliant Maximum EN 54-20Class A – 15 holes per pipe @ Alarm Level 1.1%obs/m Class B – 15 holes per pipe @ Alarm Level 3.2%obs/m Class C – 15 holes per pipe @ Alarm Level 11.5%obs/m
Threshold Settings Recommended MaximumClass A – 3 holes per pipe @ A1 to A3 Class B – 5 holes per pipe @ B1 to B5 Class C – 8 holes per pipe @ C1 to C8 Class C Escalator Mode – 8 holes per pipe @ ESC1 to ESC8 Class C Prison Mode – PR2 using Sample Head (61-988-00)
Weight3kg (6.6lbs)

Documents & Technical Downloads

Context Plus Smoke detector built in sounder

Context Plus Smoke detector built in sounder

Indicative Price

from

Simplex 4098-9714 Photoelectric Smoke Detector

Simplex 4098-9714 Photoelectric Smoke Detector

Indicative Price

from

Gentex S1209 Photoelectric Smoke Alarm, 120 VAC with 9V Battery Backup, 917-0059-002

Gentex S1209 Photoelectric Smoke Alarm, 120 VAC with 9V Battery Backup, 917-0059-002

Indicative Price

from