Single Channel Interface - 6000/MICCO
Interface Modules

Single Channel Interface - 6000/MICCO

protec·SKU: 6000/MICCO

Protec Algo-Tec™ 6000 Protocol; Loop Powered; Monitored Input Interface; Clean Contact Output Interface; Integral Short Circuit Isolator

Request a quote

Description

Our single channel interface (6000/MICCO) is a loop-powered fault-monitored input and a volt-free clean contact output interface. An on-board isolator protects against loop short circuits on incoming or outgoing loop connections.

Protec advanced addressable fire alarm systems are equipped with a wide range of interfaces that can effortlessly and efficiently integrate third-party systems. Our cutting edge 6000PLUS protocol is used for comprehensive system monitoring, ensuring that in the event of an emergency, third-party systems such as gas, plant machinery, lifts, Automatic Opening Vents (AOV’s), etc., are promptly activated or shut down to minimise damage and ensure the safety of the building and its occupants.

To make the commissioning process simple, we have incorporated our FAST™ commissioning method and equipped the interface range with an inbuilt loop short circuit isolator to enhance reliability and safety. Our fire alarm system continuously monitors our interfaces to ensure maximum protection for the building and its occupants.

Official Protec product information

Technical Specifications

BrandProtec
Clean Contact Output DetailsSingle pole changeover rated for 8 A at maximum 30 V dc non inductive
Compatible Panels6500, 6100, 6400, 6300
Detectors Supportedn/a
Dimensions (mm)147.3(W) x 86.7(H) x 10(D)
Din Rail MountedNo
Environment-10°C to +50°C (95% R.H. non condensing)
Ingress ProtectionIP20
Inputs1 x Monitored Input
IsolatorYes, on board (consult Protec DEL2110 for details)
Loop Alarm Current (Average)2.2 mA
Loop Alarm Current (Peak)5 mA
Loop PoweredYes
Loop Protocol6000/6000PLUS
Loop Quiescent Current (24V Loop Peak)0.55 mA
Loop Voltage Range16 V dc – 28 V dc peak loop
Max Number of Detectorsn/a
Number of Loop Addresses Used1
Outputs1 x Clean Contact Output
Product Code6000/MICCO
Sounders Supportedn/a
Standards / ApprovalsEN 54-17, EN 54-18 UKCA CE
Technical DocumentationDEL2109
Weight109g
Zone Quiescent Currentn/a
Zone Reset Timen/a