Single Channel Auxiliary Powered Zone Alarm Interface
Easy to Use; Reduce Installation Cost; Simple Expansion Using Existing Wiring; FAST™ Addressing; Integral Short Circuit Isolator; Auxiliary 24V dc Powered; Protec Conventional Detector and Call Point Zone; Built in Sounder Circuit Monitored for Open / Short Circuit Faults
Request a quoteDescription
The Protec 6000/APZA is a zone alarm interface which allows the 6000 series intelligent addressable loop to interface to a zone of conventional devices and a conventional sounder circuit.
This interface is ideally suited for small conventional fire detection to be fully integrated with Protec Intelligent addressable systems. The 6000/APZA is powered using an external EN54 Part 4 power supply. It can support up to 10 Protec conventional (3000PLUS) detectors.
The zone end of line is selectable using the on board DIL switch and can be programmed to resistive or capacitive as per the requirement of BS5939-1. The sounder circuit is monitored for open and short circuit faults and has 1A current drive capability.
The interface has an inbuilt loop short circuit isolator fitted as standard.
Technical Specifications
| 24V Auxiliary Voltage | 18 to 28V dc |
|---|---|
| Auxiliary 24V Current | 0.6mA Quiescent + detector load ( 13mA max ) + resistive end of line load ( 3mA ) 7.5mA Alarm, plus zone circuit current and sounder circuit current |
| Brand | Protec |
| Detectors Supported | Protec 3000 and 3000PLUS |
| Environment | -10 to 50°C (maximum 95% RH no condensation or icing) |
| Indications | On-board red indicating LED showing when the device is polled, or in the alarm state |
| Loop Alarm Current | 0.6mA |
| Loop Isolator | Yes |
| Loop Protocol | Protec Algo-tec 6000™ |
| Loop Quiescent Current | 0.6mA |
| Loop Voltage | 18 to 28V peak loop |
| Manual Call Point | Must be fitted with a 330Ω or 180Ω series resistor |
| Number of Addresses | 1 |
| Product Approval | BSI Kitemark No: KM589455 CoCP No: 0086-CPR-589456 DoP No: PFD-CPR-0059 Relevant Standard: EN54-17 & 18 CE Marked |
| Sounder Circuit Current | 1A |
| Sounder Circuit EOL² | 10kΩ ±5% ¼W |
| Sounders Supported | Protec 3000 series |
| Weight | 120g |
| Zone Circuit EOL² | Resistive – 8.2Ω ±5% ¼W Capacitive – 100µF ±20% in series with 22Ω ±5% ¼W |