4 Channel Input/Output Interface
Interface Modules

4 Channel Input/Output Interface

protec·SKU: 6000/4IO

2 x Monitored Detection Zones; 2 x Monitored Inputs; 2 x Monitored Alarm Outputs; 2 x Volt Free Changeover Contacts; Auxiliary 24vDC Powered; DIN Rail Mounted; Integral Short Circuit Isolator; Protec Algo-Tec 6000 Protocol

Request a quote

Description

The Protec 4 way input/output interface is a auxiliary powered input / output device providing 2 local zones of conventional detectors, 2 monitored inputs, 2 local monitored alarm outputs and two volt free changeover contacts. The contacts may be used to connect to ancillary equipment.

Official Protec product information

Technical Specifications

24V Auxiliary input voltage range18 to 28V dc
BrandProtec
Clean contact output details1 Single pole changeover rated for 8A maximum at 30V DC non inductive
Environmental operational limits-10 to 50ºC (maximum 95% RH no condensation or icing)
Input cabling requirementsMaximum cable resistance 6Ω per conductor Maximum cable capacitance 0.2μ F between cable conductors
LED IndicatorUse only high brightness LED (Protec stock code: NK 02-676-46)
Loop alarm current (average)0.6mA
Loop isolator fittedYes, on board (consult Protec DEL2110 for details)
Loop protocolProtec Algo-tec™ 6000 MX1
Loop quiescent current (24V loop peak)0.6mA
Loop voltage range18 to 28V peak loop
Manual Call Point requirementsMust be fitted with a series 330Ω or 180Ω resistor
Monitored input end of line detailsEnd of line resistor value 47kΩ 1/4W ±5%
Monitored input fire thresholdBelow 7.85kΩ
Monitored input open circuit thresholdAbove 111kΩ
Monitored input pre-alarm thresholdBelow 32kΩ ( Input 3 only )
Monitored input short circuit thresholdBelow 230Ω
Number of loop addresses used4 maximum, user and build configurable
Sounder circuit cable requirementsMaximum cable resistance depends on Volt drop calculations Maximum cable capacitance 0.1 F between cable conductors.
Sounder circuit end of line10kΩ ¼W ±5%
Sounder circuit fuses20mm x 5mm 1.6A Quick Blow
Sounder current limit (maximum)1.6A
Sounder open circuit fault thresholdAbove 18kΩ
Sounder short circuit fault thresholdBelow 2kΩ
Sounders supportedProtec 3000 series
Weight245g ( including din rail housing, no backbox, 4 way build )
Zone end of line requirements (I/P 1 & I/P 2)Resistive – 8.2k ±5% ¼W, Capacitive – 100μ F ±20% in series with 22Ω ±5% ¼W
Zone fire thresholdBelow 70% of supply voltage
Zone quiescent current500μ A maximum ( 10 Protec 3000 detectors per zone )
Zone reset time2 seconds, with active zone discharge
Zone resistive open circuit thresholdAbove 92% of supply voltage
Zone short circuit current (24V)26mA peak ± 2mA
Zone short circuit thresholdBelow 5% of supply voltage

Documents & Technical Downloads