Two-channel Input/Output Interface - 6000/2IO
Interface Modules

Two-channel Input/Output Interface - 6000/2IO

protec·SKU: 6000/2IO

2 x Monitored Detection Zones; 2 x Monitored Alarm Outputs; Auxiliary 24vDC Powered; DIN Rail Mounted; Integral Short Circuit Isolator

Request a quote

Description

Our 6000/2IO is a loop-powered input/output device providing two individually monitored inputs and two volt-free changeover contacts, best used to connect ancillary equipment to a Protec fire alarm system.

Protec advanced addressable fire alarm systems are equipped with a wide range of interfaces that can effortlessly and efficiently integrate third-party systems. Our cutting edge 6000PLUS protocol is used for comprehensive system monitoring, ensuring that in the event of an emergency, third-party systems such as gas, plant machinery, lifts, Automatic Opening Vents (AOV’s), etc., are promptly activated or shut down to minimise damage and ensure the safety of the building and its occupants.

To make the commissioning process simple, we have incorporated our FAST™ commissioning method and equipped the interface range with an inbuilt loop short circuit isolator to enhance reliability and safety. Our fire alarm system continuously monitors our interfaces to ensure maximum protection for the building and its occupants.

Official Protec product information

Technical Specifications

BrandProtec
Clean Contact Output Details1 Single pole changeover rated for 2 A maximum at 24 V dc (non inductive) 1 Single pole changeover rated for 8 A maximum at 24 V ac (non inductive)
Compatible Panels6500, 6100, 6400, 6300
Detectors Supportedn/a
Dimensions (mm)146.5(W) x 39(H) x 118(D)
Din Rail MountedYes
Environment-10°C to +50°C (95% R.H. non condensing)
Ingress ProtectionIP00
Inputs2 x Monitored Inputs
IsolatorYes, on board (consult Protec DEL2110 for details)
Loop Alarm Current (Average)18mA
Loop Alarm Current (Peak)n/a
Loop PoweredYes
Loop Protocol6000/6000PLUS
Loop Quiescent Current (24V Loop Peak)1.6 mA + zone end of line current + zone loading
Loop Voltage Range18 V dc – 28 V dc peak loop
Max Number of Detectorsn/a
Number of Loop Addresses Used2 maximum, user and build configurable
Outputs2 x Clean Contact Outputs
Product Code6000/2IO
Sounders Supportedn/a
Technical DocumentationDEL2118
Weight245g (including din rail housing, no backbox, 4 way build)
Zone Quiescent Currentn/a
Zone Reset Timen/a

Documents & Technical Downloads