2 Channel Ancillary Powered Zone Alarm Interface
Interface Modules

2 Channel Ancillary Powered Zone Alarm Interface

protec·SKU: 6000/2APZA

2 x Monitored Detection Zones; 2 x Monitored Alarm Outputs; Auxiliary 24vDC Powered; DIN Rail Mounted; Integral Short Circuit Isolator; Protec Algo-Tec 6000 Protocol

Request a quote

Description

The Protec 2 way auxiliary powered zone alarm interface is an auxiliary powered input / output device providing 2 local zones of conventional detectors and 2 local monitored alarm outputs.

Official Protec product information

Technical Specifications

24V Auxiliary input voltage range18 to 28V dc
BrandProtec
Environmental operational limits-10 to 50ºC (maximum 95% RH no condensation or icing)
Input cabling requirementsMaximum cable resistance 6Ω per conductor Maximum cable capacitance 0.2μ F between cable conductors
LED IndicatorUse only high brightness LED (Protec stock code: NK 02-676-46)
Loop alarm current (average)0.6mA
Loop isolator fittedYes, on board (consult Protec DEL2110 for details)
Loop protocolProtec Algo-tec™ 6000 MX1
Loop quiescent current (24V loop peak)0.6mA
Loop voltage range18 to 28V peak loop
Manual Call Point requirementsMust be fitted with a series 330Ω or 180Ω resistor
Number of loop addresses used2 maximum, user and build configurable
Sounder circuit cable requirementsMaximum cable resistance depends on Volt drop calculations Maximum cable capacitance 0.1μ F between cable conductors
Sounder circuit end of line10kΩ ¼W ±5%
Sounder circuit fuses20mm x 5mm 1.6A Quick Blow
Sounder current limit (maximum)1.6A
Sounder open circuit fault thresholdAbove 18kΩ
Sounder short circuit fault thresholdBelow 2kΩ
Sounders supportedProtec 3000 series
Weight245g ( including din rail housing, no backbox, 4 way build )
Zone end of line requirements (I/P 1 & I/P 2)Resistive – 8.2k ±5% ¼W, Capacitive – 100μ F ±20% in series with 22Ω ±5% ¼W
Zone fire thresholdBelow 70% of supply voltage
Zone quiescent current500μ A maximum ( 10 Protec 3000 detectors per zone )
Zone reset time2 seconds, with active zone discharge
Zone resistive open circuit thresholdAbove 92% of supply voltage
Zone short circuit current (24V)26mA peak ± 2mA
Zone short circuit thresholdBelow 5% of supply voltage