Potter Amseco VSR-FE2-2 Waterflow Alarm Switch with Electronic Retard, 2" Pipe
Waterflow Switches

Potter Amseco VSR-FE2-2 Waterflow Alarm Switch with Electronic Retard, 2" Pipe

Potter / Amseco·SKU: VSR-FE2-2

Indicative Price

Excluding local taxes and shipping.

The Model VSR-FE-2-2 is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 thru 40, size 2". The unit may also be used as a sectional waterflow detector on large systems. The unit contains an output relay and an adjustab

infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.

Description

The Model VSR-FE-2-2 is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 thru 40, size 2". The unit may also be used as a sectional waterflow detector on large systems.

The unit contains an output relay and an adjustable electronic retard. The relay is actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period.


Also known as: VSRFE22

Technical Specifications:
  • Contact Ratings: DPDT (Form C) 2 Amps at 30VDC or 125VAC resistive
  • Power Requirements: STANDBY: 10 mA at 120VAC or 1.5 mA at 24VAC/DC; ALARM: 40 mA at 120VAC or 35 mA at 24VAC/DC
  • Maximum Surge: 18 FPS (5,5 m/s)
  • Minimum Flow for Alarm: 10 GPM (38 LPM)
  • Service Pressure: Up to 450 PSI (31 BAR)
  • Conduit Entrances: Two knockouts provided for 1/2" conduit


  • Non-corrosive saddle bushing
  • 5-year warranty
  • Listings: UL, ULC and FM
  • Pipe schedules 10-40 Size 2”
  • NEMA 4 solid metal enclosure
  • Factory installed neoprene gasket
  • 0-90 second electronic retard
  • 450 psi system pressure rated
  • Two ½” KOs for dual voltage applications

Supplier product information

Technical Specifications

BrandPotter / Amseco
Conduit EntrancesTwo knockouts provided for 1/2" conduit
Contact RatingsDPDT (Form C) 2 Amps at 30VDC or 125VAC resistive
ListingsUL, ULC and FM
Manufacturer Part NumberVSR-FE2-2
Maximum Surge18 FPS (5,5 m/s)
Minimum Flow for Alarm10 GPM (38 LPM)
Power RequirementsSTANDBY: 10 mA at 120VAC or 1.5 mA at 24VAC/DC; ALARM: 40 mA at 120VAC or 35 mA at 24VAC/DC
Service PressureUp to 450 PSI (31 BAR)

Documents & Technical Downloads

Potter / Amseco FSBS Flowswitch Bypass Switch

Potter / Amseco FSBS Flowswitch Bypass Switch

Indicative Price

from

Potter Amseco RD13-100-0 Fire Alarm System Accessory

Potter Amseco RD13-100-0 Fire Alarm System Accessory

Indicative Price

from

Potter Amseco RD13-1.5 Residential Riser without Check Valve, 1.5" Pipe

Potter Amseco RD13-1.5 Residential Riser without Check Valve, 1.5" Pipe

Indicative Price

from

Potter Amseco RD13-1.25 Residential Riser without Check Valve, 1.25" Pipe

Potter Amseco RD13-1.25 Residential Riser without Check Valve, 1.25" Pipe

Indicative Price

from