Waterflow Switches
Potter Amseco VSG-3 Waterflow Alarm Switch for Low Flow, 3" Pipe Size
Potter / Amseco·SKU: VSG-3
Indicative Price
Excluding local taxes and shipping.
The Potter Amseco VSG-3 is a flexible vane type of waterflow switch for use in wet pipe water mist systems where a low flow for alarm is required. It is designed for installation in sections of 3" stainless steel or brass pipe with wall thickness. The unit may also be used as a sectional waterflow d
infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.
Description
The Potter Amseco VSG-3 is a flexible vane type of waterflow switch for use in wet pipe water mist systems where a low flow for alarm is required. It is designed for installation in sections of 3" stainless steel or brass pipe with wall thickness.
The unit may also be used as a sectional waterflow detector on large systems.
The unit contains an output relay and an adjustable electronic retard. The relay is actuated when a flow of 3 gallons per minute (11,4 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period.
UPC: 785192007296
Also known as: VSG3, PL-VSG3
The unit may also be used as a sectional waterflow detector on large systems.
The unit contains an output relay and an adjustable electronic retard. The relay is actuated when a flow of 3 gallons per minute (11,4 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period.
UPC: 785192007296
Also known as: VSG3, PL-VSG3
Technical Specifications:
|
- 5-year warranty
- Operates at 4 GPM, specially designed for water mist systems
- NEMA 4 solid metal enclosure
- 0-90 second electronic retard
- Listings: UL and CSFM
- 3" pipe size
- Factory installed neoprene gasket
- Two 1/2” KOs for dual voltage applications
- Non-corrosive saddle bushing
- 450 psi system pressure rated
Technical Specifications
| Brand | Potter / Amseco |
|---|---|
| Conduit Entrances | 2 knockouts provided for 1/2" conduit |
| Contact Ratings | DPDT (Form C), 2 Amps at 0-30VDC or 0-125VAC resistive |
| Flow Required for Alarm | 3.0 GPM (11,4 LPM) |
| Listings | UL and CSFM |
| Manufacturer Part Number | VSG-3 |
| Maximum Surge | 18 FPS (5,5 m/s) |
| Power Requirements | STANDBY: 10ma at 120V AC or 1.5ma at 24V AC/DC; ALARM: 40ma at 120V AC or 35ma at 24V AC/DC |
| Service Pressure | Up to 450 PSI (31 BAR) |
Documents & Technical Downloads
Related Products
View Cataloguearrow_forward
Potter / Amseco FSBS Flowswitch Bypass Switch
Indicative Price
from

Potter Amseco RD13-100-0 Fire Alarm System Accessory
Indicative Price
from

Potter Amseco RD13-1.5 Residential Riser without Check Valve, 1.5" Pipe
Indicative Price
from

Potter Amseco RD13-1.25 Residential Riser without Check Valve, 1.25" Pipe
Indicative Price
from