Gas Detectors
Macurco TX-6-ND Nitrogen Dioxide Detector, 12-24 VAC or 12-32 VDC, Dark Gray
Macurco·SKU: TX-6-ND
Indicative Price
Excluding local taxes and shipping.
The Macurco TX-6-ND is a detector, controller, and transducer for monitoring Nitrogen Dioxide Gas in parking garages, maintenance facilities, and many other commercial locations. This highly sensitive meter can monitor 0-20 ppm of nitrogren dioxide (NO2). When NO2 levels rise, the TX-6-ND automatica
infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.
Description
The Macurco TX-6-ND is a detector, controller, and transducer for monitoring Nitrogen Dioxide Gas in parking garages, maintenance facilities, and many other commercial locations.
This highly sensitive meter can monitor 0-20 ppm of nitrogren dioxide (NO2). When NO2 levels rise, the TX-6-ND automatically activates an exhaust fan to clear the air. The unit is compatible with the Macurco DVP-120 Control Panel and mounts easily to a standard 4 x 4 electrical box.
The TX-6-ND is also available in white.
UPC: 783748825103
Also known as: MA-TX6ND, TX6ND
This highly sensitive meter can monitor 0-20 ppm of nitrogren dioxide (NO2). When NO2 levels rise, the TX-6-ND automatically activates an exhaust fan to clear the air. The unit is compatible with the Macurco DVP-120 Control Panel and mounts easily to a standard 4 x 4 electrical box.
The TX-6-ND is also available in white.
UPC: 783748825103
Also known as: MA-TX6ND, TX6ND
Technical Specifications:
|
- 0.5A N.O. or N.C. Alarm Relay
- 12-24VAC or 12-32VDC input
- 5A SPDT Fan control relay
- Selectable Fan and Alarm Relay Actuation Settings
- Digital Display (0-20ppm of NO2), Internal Buzzer
- Coverage Area: 5,000 sq. ft.
- 4-20mA current loop
- Supervised system design: detector problem will cause the fan & alarm relay to activate
- Mounts on a standard 4x4 inch electrical box
- Factory calibrated
Technical Specifications
| Alarm relay | 0.5A 120 V, 60 VA |
|---|---|
| Alarm relay actuation | selectable N.O. default or N.C. |
| Alarm relay settings | 1 - 20 ppm NO2 |
| Brand | Macurco |
| Color | Dark gray |
| Connections | plugs/terminals |
| Coverage Area | 5,000 sq. ft. |
| Current @ 24 VDC | 75 mA in alarm, 50 mA fan relay on and 23 mA stand by |
| Fan relay | 5 A, 240 VAC, pilot duty, SPDT |
| Fan relay actuation | selectable at OFF, 0.2, 0.5, 0.7, 1.0, 1.2, 1.5, 1.7, 2.0, 2.2, 2.5 (default), 2.7, 3.0, 3.2, 3.5, 3.7, 4.0, 4.2, 4.5, 4.7, 5.0 ppm |
| Manufacturer Part Number | TX-6-ND |
| Mounting box | (not included) 4x4 electric |
| Operating Environment | 0°F to 125° F (-18°C or above 52°C).10 to 90% RH |
| Power | 3 W (max) from 12 to 24 VAC or 12 to 32 VDC |
| Shipping Weight | 1 pound (0.45 kg) |
| Size | 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm) |
| Supervised system design | detector problem will cause the fan & alarm relay to activate |
| UPC | 783748825103 |
Documents & Technical Downloads