Macurco CM-6 Carbon Monoxide Detector, Controller and Transducer, 12-24 VAC or 12-32 VDC
Indicative Price
Excluding local taxes and shipping.
The Macurco CM-6 is a low-voltage carbon monoxide detector and ventilation controller with a 0-200 ppm CO measurement range, 5A SPDT fan relay, and 4-20 mA analog output for commercial parking garages, boiler rooms, and vehicle maintenance facilities. Operating on 12-24 VAC or 12-32 VDC, it features
Description
The Macurco CM-6 is a low-voltage carbon monoxide detector and ventilation controller with a 0-200 ppm CO measurement range, 5A SPDT fan relay, and 4-20 mA analog output for commercial parking garages, boiler rooms, and vehicle maintenance facilities. Operating on 12-24 VAC or 12-32 VDC, it features a configurable 0.5A alarm relay, adjustable ventilation thresholds, programmable fan delays, and optional digital concentration display and audible buzzer. The CM-6 provides coverage of up to 7,500 square feet per detector and is ETL Listed to UL 2075.
Macurco CM-6 Carbon Monoxide Detector and Ventilation Controller
The Macurco CM-6 is a low-voltage carbon monoxide (CO) detector, automatic ventilation controller, and analog gas transducer designed for commercial and industrial air-quality monitoring. Part of Macurco's 6 Series fixed gas detection platform, the CM-6 continuously measures carbon monoxide concentrations from 0 to 200 parts per million (ppm) and activates connected ventilation or alarm equipment when configured gas concentration thresholds are reached. The detector is designed for enclosed parking garages, vehicle maintenance facilities, boiler rooms, loading docks, and other indoor environments where combustion equipment and vehicle exhaust can produce hazardous CO concentrations. Its integrated control circuitry allows the CM-6 to function independently as a gas detector and ventilation controller or as part of a larger monitoring system connected to compatible Macurco control panels and building automation equipment. Macurco's current product specifications identify a coverage area of up to 7,500 square feet per detector, although actual placement and detector quantity depend on building layout, airflow, occupancy conditions, and applicable mechanical and fire safety requirements.
The Macurco CM-6 operates on 12-24 VAC or 12-32 VDC power with a maximum consumption of 3 watts, allowing integration with compatible low-voltage power supplies and commercial gas monitoring systems. At 24 VDC, the detector draws approximately 23 mA in standby, 50 mA with the fan relay energized, and 75 mA during alarm. The unit incorporates a 5-amp single-pole, double-throw (SPDT) fan control relay rated for 240 VAC pilot duty, enabling automatic operation of appropriately rated ventilation fan starters and associated control circuits. Programmable fan activation thresholds allow the ventilation system to respond to measured CO concentrations, with settings of 25, 35, 50, or 100 ppm documented in the manufacturer's operating instructions. Adjustable fan delays of 0, 1, 3, 5, or 10 minutes and configurable minimum fan runtimes help reduce unnecessary equipment cycling while maintaining ventilation operation after elevated CO conditions are detected. A separate 0.5-amp alarm relay rated at 120 VAC, 60 VA supports normally open or normally closed signaling to compatible alarm panels, warning devices, and building management systems. Supported alarm thresholds include 50, 100, 150, and 200 ppm, with factory default settings of 35 ppm for ventilation activation and 200 ppm for alarm signaling.
The CM-6 features a 4-20 mA analog current-loop output corresponding to carbon monoxide concentrations from 0 to 200 ppm, allowing continuous gas concentration monitoring through compatible Macurco controllers, building automation systems, and other analog monitoring equipment. Its configurable three-digit LED display provides local CO concentration readings when enabled, while an integrated audible buzzer can produce an approximately 85 dBA warning measured at 10 centimeters during alarm conditions. Both the display and buzzer can be enabled or disabled through the detector's configuration settings. The unit also incorporates internal fault supervision, with programmable responses for ventilation and alarm relays when a detector malfunction occurs. Its menu-driven programming interface allows technicians to adjust alarm thresholds, fan operation, output settings, and diagnostic functions directly at the device. The CM-6 uses an electrochemical carbon monoxide sensing element and supports functional gas testing and field calibration using approved Macurco calibration accessories and certified CO test gas. These features provide the flexibility to configure the detector for standalone ventilation control, local gas monitoring, or centralized commercial CO detection systems.
The Macurco CM-6 features a compact enclosure measuring 4-1/2 inches high, 4 inches wide, and 2-1/8 inches deep, designed for mounting directly over a standard 4-inch square electrical box, which is purchased separately. Its plug-in terminal connections provide interfaces for low-voltage power, ventilation relay control, auxiliary alarm signaling, and analog communication. The detector operates in ambient temperatures from 0 F to 125 F (-18 C to 52 C) and supports relative humidity from 10% to 90%, noncondensing. It is ETL Listed to UL 2075 for gas and vapor detection applications and is intended for commercial carbon monoxide monitoring rather than replacement of required residential household CO alarms. Unlike the Macurco CM-12, which operates directly on 100-240 VAC line voltage, the CM-6 uses low-voltage AC or DC power while providing similar ventilation control, alarm signaling, and 4-20 mA monitoring capabilities. Optional accessories include the Macurco WHK-1 weatherproof housing, CM-CH calibration hood, compatible calibration gas kits, and Macurco gas detection control panels. Its combination of configurable CO thresholds, automatic fan control, analog concentration reporting, alarm supervision, and compact installation makes the CM-6 suitable for commercial parking structures, mechanical rooms, warehouses, and vehicle exhaust ventilation systems requiring dependable carbon monoxide detection and control.
UPC: 051131495807
Also known as: MA-CM6, CM6
Technical Specifications:
|
- Supervised system: any internal detector problem will cause the fan & Alarm relay to activate
- ETL Listed to UL 61010-1
- Low level meter capable of displaying from 0-200 ppm of CO
- The CM-6 meets the requirements of the Uniform Building Code for enclosed garages and meets
- OSHA standards for CO exposure
- Selectable fan and alarm relay activation
- 5 A SPDT fan relay controls starters of exhaust fans 0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
- 4-20 mA Current Loop
- CM-6 mounts on a standard 4x4 electrical box and becomes cover for the box
- Optional calibration kit is available. One screw allows access for calibration or gas test
Technical Specifications
| Alarm relay | 0.5A 120 V, 60 VA |
|---|---|
| Alarm relay actuation | selectable N.O. default or N.C. |
| Alarm relay settings | OFF, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default) |
| Brand | Macurco |
| Color | Dark gray |
| Connections | plugs/terminals |
| Current @ 24 VDC | 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by |
| Fan relay | 5 A, 240 VAC, pilot duty, SPDT |
| Fan relay actuation | selectable at 25 ppm, 35 ppm (default), 50 ppm or 100 ppm CO |
| Manufacturer Part Number | CM-6 |
| Mounting box | (not included) 4x4 electric |
| Operating Environ | 0°F to 125° F (-18C or above 52C) 10 to 90% RH |
| Power | 3 W (max) from 12 to 24 VAC or 12 to 32 VDC |
| Shipping Weight | 1 pound (0.45 kg) |
| Size | 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm) |
| Supervised system | any internal detector problem will cause the fan & Alarm relay to activate |
| UPC | 051131495807 |