MI/DISO — Isolator Module
Isolator Module The loop isolator module is used on the Morley-IAS intelligent fire alarm control panels to protect the system against wire-to-wire short circuits on the analogue addressable loop wiring. The fault isolator modules should be placed between groups of sensors on the loop wiring to prot
Request a quoteDescription
Isolator Module
The loop isolator module is used on the Morley-IAS intelligent fire alarm control panels to protect the system against wire-to-wire short circuits on the analogue addressable loop wiring. The fault isolator modules should be placed between groups of sensors on the loop wiring to protect the loop if a short circuit fault occurs. If a short circuit fault occurs, the two isolators located either side of the short circuit fault will automatically sense the voltage drop, open their switches and remove the devices from the rest of the loop.
Technical Specifications
| Model / reference | MI/DISO |
|---|