The HCU-2000 controller is the core unit of Honeywell’s Intevio PAVA systems. It effortlessly performs multiple critical functions like audio storage and playback, signal processing, zone control, routing, scheduled broadcasts, supervision and fault detection. It meets international standards for safety. With its built-in 500W Class-D amplifier, this single controller can work as an integrated, 8-zone PAVA system for better stability, cost savings and superb user experience.
FEATURES- AC 220-240 V, 50 / 60 Hz
Main Power Supply Voltage - 750 W
Rated Power
- AC 220-240 V, 50 / 60 Hz
Backup power supply voltage - T10AH 250 V
Main Power Supply Fuse
- 85 Hz-18 KHz
Mic/Line Frequency Response - 14.3Kg
Net Weight
Technical Specifications
| abc | 24V/1A |
|---|---|
| Amplifier Control Interfaces Channels | 3 (channel 1, channel 2 and backup amplifier) |
| Amplifier Control Interfaces Control Signal | Self-test signal, amplifier fault signal and power saving control signal |
| Amplifier Control Interfaces Output Signal | 1.4V |
| Amplifier Control Interfaces THD | <0.5% |
| Audio Output Channels | Channel 1, channel 2 and recording output |
| Audio Output signal | 1V (0dBV) |
| Audio Output THD | <0.5% |
| Auxiliary input Frequency response | 85Hz-18KHz |
| Auxiliary input Input channels | 2 |
| Auxiliary input Input impedance | 10 KΩ |
| Auxiliary Input Sensitivity | 1V (0dBV) |
| Auxiliary Input SNR | >77dB (with A-Weight) |
| Backup power supply | AC 220-240V, 50/60Hz |
| Call Station Interface Frequency Response | 85Hz-18KHz |
| Call Station Interface Input Impedance | 20 KΩ |
| Call Station Interface Input Signal | 2V |
| Call Station Interface Output Impedance | 20 KΩ |
| Call Station Interface Output Signal | 2V |
| Contact Inputs | 10 (monitored) |
| Contact Outputs | 8 (NO, NC & COM), “fault output, emergency output |
| DC power output | 24V/1A |
| Ethernet Port | 10M/100M |
| Gross Weight | 17.4Kg |
| Humidity | < 95%, without condensation |
| Loudspeaker Circuits Load | 500W |
| Loudspeaker Circuits Output Channels | 8 (with group A and group B) |
| Main Power Supply Fuse | T10AH 250V |
| Main Power Supply Voltage | AC 220-240V, 50/60Hz |
| MAX. Working current for Outputs | 2.5A |
| MAX. Working Voltage for Outputs | AC 250V/DC 30V |
| Memory Capacity | 1GB |
| Mic/Line Input Frequency Response | 85Hz-18KHz |
| Mic/Line Input Impedance | 10 KΩ |
| Mic/Line Input Phantom Power | DC 24V, switchable |
| Mic/Line Input Sensitivity | -50dBV/0dBV, selectable |
| Mic/Line Input SNR | >77dB (with A-Weight) |
| Microphone Input Frequency Response | 90 Hz -13KHz |
| Microphone Input Impedance | 250Ω |
| Microphone Input Sensitivity | -65±3dBV |
| Microphone Input SNR | >50dB (with A-Weight) |
| Model / reference | HCU-2000 |
| Model No. | HCU-2000 |
| Monitoring Loudspeaker | 2W/8Ω |
| Net Weight | 14.3Kg |
| Operating Temperature | -10°C~+50°C (14°F~+122°F) |
| Package dimension (W×H×D) | 580 mm×279 mm×552 mm |
| Product dimensions (W×H×D) | 482 mm×133.5 mm×420 mm |
| Rated Power | 750W |
| Storage Temperature | -40°C~+70°C (-40°F~+158°F) |