ECS-500/502 — Pre-Engineered Automatic Electrical Cabinet Fire Suppression System
Pre-Engineered Automatic Electrical Cabinet Fire Suppression System Honeywell’s ECS-500 and ECS-502 are Direct Low Pressure systems filled with 2.27 kg of kg of non-toxic and odourless FK-5-1-12 fire suppression agent. Each cylinder assembly is pre-pressurised to 240psi (16Bar) and operates in a tem
Request a quoteDescription
Pre-Engineered Automatic Electrical Cabinet Fire Suppression System
Honeywell’s ECS-500 and ECS-502 are Direct Low Pressure systems filled with 2.27 kg of kg of non-toxic and odourless FK-5-1-12 fire suppression agent. Each cylinder assembly is pre-pressurised to 240psi (16Bar) and operates in a temperature range of -17.8° C to 54.4° C. It comes with an EOL adapter (with gauge) and cylinder valve Assy, 4 rubber grommets, 25 plastic loop clamps and a cylinder mounting bracket.
The assembly is installed on-site with the included bracket. The Heat detection tube is installed inside the electrical panel using the included rubber grommets and plastic loop clamps. The tube is pressurized with dry Nitrogen to 16 Bar using the Filling Adapter and connected to the cylinder valve assembly on-site. The EOL Adapter with gauge is connected at the end of the tube. The pressure gauge is kept outside the electrical panel for clear visibility and to ease inspection. The ball valve on the cylinder valve assembly is kept in the “ON” position to complete the installation and commissioning.
Technical Specifications
| Model / reference | ECS-500/502 |
|---|