DOM4-24 — Digital Output Module (DOM) with 24 zones
Digital Output Module (DOM) with 24 zones The DOM4-24 offers all the functions of an alarm and evacuation system in a 19" module. It has interfaces to all input/output modules, manages and monitors the loudspeaker, and operates 6 zones. With features like ongoing Automatic Volume Control (AVC), auto
Request a quoteDescription
Digital Output Module (DOM) with 24 zones
The DOM4-24 offers all the functions of an alarm and evacuation system in a 19" module. It has interfaces to all input/output modules, manages and monitors the loudspeaker, and operates 6 zones. With features like ongoing Automatic Volume Control (AVC), automatic and dynamic switching, and emergency power supply, the DOM4-24 is ideal for use in emergencies where specific acoustic alarms are critical.
FEATURES- 100 Hz to 8 kHz
Sensor Input (AVC*) Transmission range - 24 W
Power consumption
- min. 5 kΩ, max. 500 pF
Load impedance - 0 dB
Audio Output Nominal level
- 15 % to 90 %
Relative humidity - 6.8 kg
Weight
Technical Specifications
| Ambient temperature | -5°C to +55°C |
|---|---|
| Audio Output Harmonic distortion at the nominal level | < 0.03 % at 1 kHz |
| Audio Output Max. deviation from the linear transmission | ±1 dB in transmission range |
| Audio Output Max. harmonic distortion | 0.1 % in transmission range |
| Audio Output Max. output level | +6 dB |
| Audio Output Nominal level | 0 dB |
| Audio Output Transmission range | 20 Hz to 20 kHz |
| Audio Output type | electronically balanced |
| Connection Contacts Max. voltage | 250 V AC, 30 V DC / 5 A |
| Connection Contacts Surge voltage resistance | > 1.5 kV |
| Control Contacts Max. voltage | 100 V DC / 1 A |
| Control Contacts Surge voltage resistant | > 2.5 kV |
| Dimensions (W x H x D) | 483 x 44 x 345 mm/1 HE, 19” |
| Emergency Power Supply Nominal voltage | 24 V DC |
| Emergency Power Supply Power consumption | 24 W |
| Load impedance | min. 5 kΩ, max. 500 pF |
| Mains Voltage Frequency range | 47 Hz to 440 Hz |
| Mains Voltage Power consumption DOM4-24 with/without 4 x DAL | 50 W/80 W @ 230 V AC |
| Mains Voltage Voltage range | 90 V AC to 264 V AC |
| Model / reference | DOM4-24 |
| Model No. | DOM4-24 |
| Relative Humidity | 15 % to 90 % |
| Sensor Input (AVC*) Harmonic distortion at the nominal level | < 0.2 % at 1 kHz |
| Sensor Input (AVC*) Input type | symmetric ungrounded |
| Sensor Input (AVC*) Load impedance | typ. 200 Ω |
| Sensor Input (AVC*) Max. harmonic distortion | 1 % in transmission range |
| Sensor Input (AVC*) Nominal level | -51 dB |
| Sensor Input (AVC*) Transmission range | 100 Hz to 8 kHz |
| Unweighted signal-to-noise ratio at the nominal level | > 75 dB (A) > 70 dB |
| Weight | 6.8 kg |