2XD250 — Variodyn D1 Class-D Power Amplifier | 2 x 250W | 80?ficiency factor
Amplifiers

2XD250 — Variodyn D1 Class-D Power Amplifier | 2 x 250W | 80?ficiency factor

Honeywell·SKU: 2XD250

Variodyn D1 Class-D Power Amplifier | 2 x 250W | 80?ficiency factor The 2XD250 power amplifier offers superior control and monitoring via the Variodyn D1’s DOM. It provides enhanced electronic protection against thermal overload and short-circuits during output. A low power socket for the connection

Request a quote

Description

Variodyn D1 Class-D Power Amplifier | 2 x 250W | 80?ficiency factor

The 2XD250 power amplifier offers superior control and monitoring via the Variodyn D1’s DOM. It provides enhanced electronic protection against thermal overload and short-circuits during output. A low power socket for the connection of the mains voltage and mains fuse are located in the rear. The power amplifier can only be operated via a three-wire system feed with a protective ground wire.

FEATURES
  • 2 x 250 W
    Rated power output (sin.)
  • 2.8 A
    Voltage consumption (230 V AC)
  • > 20 kΩ, el. balanced
    Input impedance
  • 50 to 60 Hz, +10% / -5%
    Nominal frequency
  • 40% to 93%, (no condensation)
    Relative humidity
  • 24 V DC
    Emergency power supply

Official manufacturer product information

Technical Specifications

Ambient temperature during operation-5°C to +55° C
Dimensions (B x H x T)483 x 88 x 402 mm / 2 HU, 19”
Dissipation loss / 230 V AC (Idle)25 W max.
Dissipation loss / 24 V DC (channels off)3 W max
Dissipation loss / 24 V DC (channels on)10 W max
Emergency power supply24 V DC
functional principalClass D
Harmonic distortion at full load / 1 kHz< 0.03 % Channel separation > 42 dB
Housing colourgray, similar to RAL 7016
Input impedance> 20 kΩ, el. balanced
Model / reference2XD250
Model No.2XD250
Net Weightapprox. 16.5 kg
Nominal frequency50 to 60 Hz, +10% / -5%
Nominal voltage230 V AC
Rated power output (sin.)2 x 250 W
Relative Humidity40% to 93%, (no condensation)
Signal-to-noise ratio> 90 dB, A - unweighted
Transmission frequency band50 Hz to 22 kHz
Transmission frequency band (-1 dB)50 Hz to 22 kHz
Voltage consumption (230 V AC)2.8 A
Voltage consumption (24 V DC / Announcement / 1/3 load) *8.75 A
Voltage consumption (24 V DC / Announcement / 1/8 load) *3.6 A
Voltage consumption (24 V DC / Sinus continuous tone*)25 A