S4 Interface Modules
S4 Interface Modules 4-Input / Output Interface Module are designed for use with Vigilon and 34000 fire alarm control panel
Request a quoteDescription
S4 Interface Modules input/output interface module can be configured to provide any combination of up to four inputs or outputs. An output of either normally open or normally closed relay contacts can be used to control a load of up to 1A @ 30V DC/ac .
Each module includes a loop isolator for device isolation. Each interface module use one of 207 available device addresses on a loop and responds to regular polls from the control panel reporting the type of device and the status
The S4 interface modules can be mounted in other equipment housings using the DIN rail mount brackets can also be fitted into a plastic box
An input can be programmed as a fire, fault, supervisory or confirmation input. Additionally it is possible for channel 1 to be used as a Zone input, which allow connection of conventional detectors and MCPs to this module. Zone input can be configured to have alarm validation feature and configurable reset time
Features & Benefits:- Analogue addressable communications
- Built-in type identification automatically identifies these devices to the control panel
- Reliable communication technique with high noise immunity
- Soft or SAFE addressing
- Common mounting options including surface mount, panel mount and DIN rail mount
- Dual-colour LEDs Plug-in
- terminal connections for ease of wiring
- EN54-17:2005
- EN54-18:2005
- BS EN50130-4: 1996: Part 4
- BS EN 60950-2002
Technical Specifications
| BS EN50130-4 | 1996: Part 4 |
|---|---|
| EN54-17 | 2005 |
| EN54-18 | 2005 |
Documents & Technical Downloads
Loop Powered Interfaces Datasheet
Data Sheet · en
S4 - Low Voltage Interface Installation Manual
Installation Manual · en
Base for ES Detect Range (805590-D) Installation Manual (Issue 2)
Installation Manual · en
Base for ES Detect Range (805590-D) Installation Manual (Issue 1)
Installation Manual · en
Vigilon Advanced Fire Detection and Alarm System Operations & Maintenance Manual
Operation And Maintenance Manual · en
S4 - Low Voltage Interface Installation Manual
Installation Manual · en
Interface Module for Vigilon Low Voltage (LV) Input/Output Installation Manual
Installation Manual · en
Vigilon Advanced Fire Detection and Alarm System Installation Manual
Installation Manual · en
Interface Module for Vigilon Low Voltage (LV) Input/Output Installation Manual
Installation Manual · en
ES Detect Range Compatibility with Control Panels TB10219
Technical Bulletin · en
Interfaces on Vigilon and Compact with Loop Software 4.36 or Earlier TB10120
Technical Bulletin · en
Gent Nano Consultant's Specification Guide
Reference Guide · en
Generic Commissioning Instructions for Vigilon Plus Panel, Vigilon Compact Plus Panel and Vigilon Plus Nodes Based Fire Detection and Alarm System User Manual
User Manual · en
Generic Commissioning Instructions for Vigilon Plus Panel, Vigilon Compact Plus Panel and Vigilon Plus Nodes Based Fire Detection and Alarm System User Manual
User Manual · en
Vigilon Plus Consultant's Specification Guide
Reference Guide · en
Vigilon Panel - Sound and Resound Alarms Options Reference Guide
Reference Guide · en
Vigilon Analogue Addressable Fire Detection and Alarm System User Manual
User Manual · en
S4-34450 Product Carbon Footprint Report
Sustainability Document · en
Related Products
View Cataloguearrow_forward
Edwards SIGA-IOI FG, Module, Input/Output;SIGA-IOI
Indicative Price
from
Edwards 4-AUDTELS-E Audio and Telephone Interface/Riser Module, Europe, Edwards
Indicative Price
from