FS24X Plus Flame Detector
Flame Detectors

FS24X Plus Flame Detector

Gamewell·SKU: GWF-F-1714252

Triple IR flame detector using Honeywell’s WideBand IR™ infrared technology to detect hydrocarbon and hydrogen fires

Request a quote

Description

The FS24X Plus is a triple IR flame detector using Honeywell’s WideBand IR™ infrared technology to detect hydrocarbon and hydrogen fires quickly and reliably — before they grow — even in the presence of environmental inhibitors like rain, fog, and smoke.
Designed for hazardous locations, the FS24X Plus has several marine certifications and is SIL2 rated for safety instrumented system applications.
Features & Benefits:
  • Reliable Detection
  • Fast response to a wide range of hydrocarbon and hydrogen fires even in low visibility conditions
  • Advanced diagnostics including window clarity to maintain site protection Easy to Use
  • Sunshade and standard or marine mounting bracket included for quickly and easily positioning the detector in an optimal location.
  • Powerful FlameManager software replaces legacy dip switches for detector configuration and provides simplified diagnostics and post event FirePics™.
At a Glance Instrument Status
  • High Visibility, Multi Color LED HALO ring provides clear indication of device status from up to 50ft (15m) away, even in bright outdoor environments
Quick Specs:
  • Long-range, wide-angle sensors detect fires at 200ft (60m) for 1ft2 (0.1m2) n-Heptane
  • Multiple outputs including 4-20mA, Relays, HART®, and Modbus communication all standard
  • Responds to a wide range of hydrocarbon fires such as n-Heptane, Methane, Butane, Propane, Ethanol, Methanol, Diesel, Kerosene, JP-4, and IPA as well as Hydrogen
  • Speed of response typically 5 seconds
Even the best products deserve expert maintenance!

Elevate your gas detectors’ potential with Honeywell's expert maintenance services! Maximize uptime, eliminate costs, and ensure on-time, on-budget project completion.

Explore our fixed, portable, and high-tech support services now!

Official manufacturer product information

Additional manufacturer specifications

  • Certifications - Hazloc: ATEX: II 2 G Ex db IIC T5 Gb; II 2 D Ex tb IIIC T135° C Db IP66/67; CCC; CU-TR; IECEx: Ex db IIC T5 Gb; Ex tb IIIC T135° C Db IP66/67; INMETRO; cFMus: Class I, Div 1, Grps A,B,C,D; Class II/III, Div 1, Grps E,F,G NEMA 4X
  • Features & Benefits: At a Glance Instrument Status; Easy to Use; High-visibility halo light ring; Modbus, HART®, 4-20 mA, Relays Standard; Mounting bracket and sunshade included; Multiple Outputs; Multiple marine certifications; Proved triple IR sensor technology; Reliable Detection; Robust; Simple Maintenance
  • Application: Aircraft Hangars; Chemical Production, Storage and Loading Facilities; Loading and Unloading Facilities for Liquefied Petroleum and Natural Gas; Natural Gas/Compressed Natural Gas Plants; Oil and Gas Pipelines and Pumping Stations; Paint and Solvent Storage; Power Plants; Production and Storage Facilities for Ethanol, Methanol and Isopropanol; Tank Farms and Storage Facilities for Crude Oil and Gasoline; Turbine/Compressor Enclosures; Water Treatment Plants

Technical Specifications

Analog Output Signal Type4-20mA standard
Analog Outputs4 to 20 mA
BrandHoneywell; Honeywell; NOTIFIER
Certifications - OtherIEC61508 SIL 2 Certified by TUV Sud; IEC61508 SIL 2 Certified by TUV Sud; Maritime Type approved to ABS, Lloyds, BV, DNV
Certifications - PerformanceEN54-10: Class1 (Medium, High, Very High Sensitivities), Class 2 (Low Sensitivity); FM3260
Conduit Entries(2) 3/4 in NPT
Connector Type2 x M25 or 2 x ¾” NPT Entries
Datalogging5000 events and ten 30-second FirePics™
Digital Communication PortsHART® with Handheld Communicator or Hardwired; RS485: Modbus and FP2; USB: FP2
Enclosure Material316 Stainless Steel; Low Copper Aluminum with Marine Grade Paint
Field of View120° Cone of Vision (50% on Axis Range); 90° Cone of vision
Humidity Range0 to 99% RH; 0–99% relative humidity
IndustryEnergy
Ingress ProtectionIP66/67; IP66/67 (Type 4X)
Material316 Stainless Steel; Low Copper Aluminum with Marine Grade Paint
Minimum Temperature-55°C
NEMA RatingType 4X
Number of Analog Outputs1
Number of Relay Outputs3
Operating Current1.8 Watts (Nominal); 12 Watts (max) = with heater ON 100% duty cycle.; 2.4 Watts (Alarm)
Operating VoltageNominal: 24 VDC; Regulated: 18 to 32 VDC
Power ConsumptionAlarm: 2.4W; Nominal: 1.8 W; With Heater ON 100% Duty Cycle: 12W (Max)
Relay Activation SettingsSingle Pole Double Throw (SPDT)
Relay IncludedYes
Relay Output ConfigurationAlarm, Fault, and Auxiliary; Alarm, Fault, and Auxiliary: SPDT1 (NO2/NC3), De-Energized/Energized, Latching/Non-Latching Rating: 2A @32 VDC
Relay Rated Load2A at 32 VDC
Replacement PartsFS24XP-PUCK
Response Time5 sec and a max of 10 sec (FM Witnessed); Typically, 5 Seconds and a maximum of 10 Seconds
Sensing MethodTriple IR
SensitivityHigh 150 ft (45m); Low 50 ft (15m); Medium 100 ft (30m); Very High 200 ft (60m) to 1 ft2 (0.1 m2)
Storage Temperature-55 to +85°C
Visual IndicatorsLED halo light ring - Green, Yellow, Red
Weight rangeAluminum: 1.7 kg (3.7 lbs); Stainless Steel: 3.4 kg (7.4 lbs)