Gamewell-FCI  Elevate™ Transmitter Module
Interface Modules

Gamewell-FCI Elevate™ Transmitter Module

Gamewell·SKU: GWF-F-4059035

The TM-8 is a transmitter module that communicates on the AIO Bus (Annunciator Input/Output) for fire alarm control panels on the Gamewell-FCI Elevate™ Platform.

Request a quote

Description

The TM-8 Transmitter Module provides the GFP-A/GFP-AR fire alarm control panels on the Gamewell-FCI ElevateTM Platform with eight programmable Form-C relays, along with either remote station service featuring three reverse-polarity outputs (Alarm, Trouble, and Supervisory) or a single municipal fire alarm box trip output on one PC board.
Features & Benefits:
  • Customizable 80-character Primary label per module.
  • On each TM-8 module, either the three reverse-polarity outputs (alarm, trouble, and supervisory) or the fire municipal box trip can be used.
  • Connects to the internal AIO bus and mounts inside the GFP-A/GFP-AR cabinet on the PMB’s right-side option card position.
  • The power run to the module does not need to contain a power supervision relay since loss of power or communication is inherently supervised through AIO communication bus.
  • Diagnostic LEDs: green for Power, AIO bus Data Reception and AIO Data Transmission status; yellow for Trouble.
  • Out of the three reverse polarity outputs, Remote Station Supervisory circuit can be reprogrammed for other functions using the panel programming tool.
  • Remote Station Alarm circuit provides the option to combine trouble indication on the Alarm contact.
  • Programmable participation in Trouble Delay for AC fail condition when using Remote Station Service.
  • Programmable participation in Alarm Delay for PAS for the Remote Station Service and Master box Trip.
  • Programmable option to cancel Alarm indication when signals are silenced for remote station and municipal box trip.
  • Total of 8 programmable Form-C Relays:
    - Four low-current
    - Four higher current relays
  • The higher current relays can also be used to switch inductive loads (0.35PF).
  • The Relay 1 is predispositioned to be a fail safe trouble indication but can be reprogrammed.
  • Each of the 8 relays can be mapped to activate with a local or network:
    - Event condition (i.e. fire, CO, supervisory, etc.)
    - Activation of a point (i.e. detector, module)
    - Activation of a zone (general zone, logic zone, releasing zone states, special function zone)
  • Isolated 24 V for the Remote Station reverse-polarity outputs.
  • Remote Station Disconnect mechanism can be initiated from the panel display. It provides a means for inhibiting alarm status changes, which cause trouble indication for unit at the FACP. Operation of the disconnect mechanism will also create a trouble condition on the reverse-polarity output circuits or the master box trip
Certifications:
The TM-8 is designed to meet NFPA 72 requirements for Auxiliary Protective Signaling Systems and Remote Station Protective Signaling Systems.

    Official manufacturer product information

    Technical Specifications

    Alarm current189 mA at 24 VDC, all relays energized
    Diagnostic LEDsgreen for Power, AIO bus Data Reception and AIO Data Transmission status; yellow for Trouble.
    Dimensions (W x H)Approximately 4.375 x 7 inches
    Manufacturer modelTM-8
    Operating temperature0-49 degrees C
    Operating voltageFiltered, non-resettable 24 VDC
    Programmable relays8 Form-C relays; four low-current and four high-current
    Remote station outputsThree isolated reverse-polarity outputs; 15 mA maximum per output
    Standby current81 mA at 24 VDC
    Total of 8 programmable Form-C Relays- Four low-current - Four higher current relays

    Documents & Technical Downloads