Fire Alarm Power Supply Units
Fire-Lite CHG-75 Battery Charger
Firelite by Honeywell·SKU: CHG-75
Indicative Price
Excluding local taxes and shipping.
The Fire-Lite CHG-75 is a charger for sealed lead acid batteries used by Fire Alarm Control Panels as emergency backup power supplies. The charger comes equipped with diagnostic LEDs, trouble input and output connectors, and three fuses for overload protection. The charger connects to the SLC of a f
infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.
Description
The Fire-Lite CHG-75 is a charger for sealed lead acid batteries used by Fire Alarm Control Panels as emergency backup power supplies.
The charger comes equipped with diagnostic LEDs, trouble input and output connectors, and three fuses for overload protection. The charger connects to the SLC of a fire alarm control panel and mounts in a BB-26 or BB55F enclosure.
UPC: 783008104702
Also known as: FL-CHG75, CHG75
The charger comes equipped with diagnostic LEDs, trouble input and output connectors, and three fuses for overload protection. The charger connects to the SLC of a fire alarm control panel and mounts in a BB-26 or BB55F enclosure.
UPC: 783008104702
Also known as: FL-CHG75, CHG75
Technical Specifications:
|
- Diagnostic LEDs for monitoring: Primary AC On, Charger
- Connectors for trouble input and output
- Charger can connect to the Signaling Line Circuit (SLC) of a FireLite addressable intelligent control panel for trouble monitoring
- Mounts in a BB-26 or BB-55F enclosure
- Three fuses for overload protetction
- Screw terminal connections for battery, battery backup to other equipment and SLC loop
- AC loss reporting delay option for 8- or 16-hour delay
- Battery, charger, and AC voltage supervision
- Trouble, Ground Fault, Charging, SLC Communication
- Low Battery
Technical Specifications
| Battery sizes | 25 AH to 75 AH |
|---|---|
| Brand | Fire-Lite |
| Diagnostic LEDs for monitoring | Primary AC On, Charger |
| Float charge voltage | 27.6 VDC. |
| Form-C relay (TB4) | 2.0 A at 30 VDC (resistive). |
| Manufacturer Part Number | CHG-75 |
| Maximum charging current | 4.5 A (peak). |
| Primary AC power in (TB1) | 120 VAC, 60 Hz, 2.0 A; or 220/240 VAC, 50 Hz, 1.0 A. Wire size: minimum 14 AWG (2.0 mm²) with 600-volt insulation |
| UPC | 783008104702 |