Fike FIK-IR3 Hydrocarbon Flame Detector
Flame Detectors

Fike FIK-IR3 Hydrocarbon Flame Detector

Fike·SKU: FIK-IR3

Triple-spectrum infrared detector for hydrocarbon fires. Ultra-fast mode detects fireballs or explosions within 40 milliseconds; standard-fire response depends on fuel, distance and sensitivity.

Request a quote

Description

Triple-spectrum infrared detector for hydrocarbon fires. Ultra-fast mode detects fireballs or explosions within 40 milliseconds; standard-fire response depends on fuel, distance and sensitivity.

  • Function: Hydrocarbon flame detector
  • Benefit: Detection within 40 milliseconds of fireballs or explosions; detects standard fires 50 ft away within 1.3 seconds, and fires 230 ft away within 3.7 seconds.
  • Manufacturer listed standards and approvals: ATEX | IECEx | FM | FMC | CSFM | INMETRO

Official Fike product information

Technical Specifications

BrandFike
Conduit entries2 x 3/4 in 14 NPT or M25 x 1.5
Detection rangeStandard fires 50 ft (15 m) away within 1.3 seconds
Detection technologyMulti-spectrum infrared (IR3)
Detector weight (stainless steel 316)6.6 lb (3.0 kg)
Hazardous area approvalsATEX II 2 G D Ex db IIC T5/T4 Gb; IECEx; Class I Div. 1 Groups B, C and D; Class I Zone 1 AEx/Ex db IIC
HumidityUp to 99% RH, non-condensing
Ingress protectionIP66 and IP68 (2 m, 24 hr); NEMA 4X and 6P
Operating temperature-67°F to +167°F (-55°C to +75°C); -67°F to +185°F (-55°C to +85°C) with the extended option
Response timeWithin 40 milliseconds of fireballs or explosions
Standby current120 mA; 180 mA with all systems in operation including window heater
Storage temperature-67°F to +185°F (-55°C to +85°C)
Tilt mount weight (stainless steel 316)3.3 lb (1.5 kg)
Wiring12-20 AWG (2.5-0.35 mm2)