Triple-spectrum infrared detector for hydrocarbon fires. Ultra-fast mode detects fireballs or explosions within 40 milliseconds; standard-fire response depends on fuel, distance and sensitivity.
Request a quoteDescription
Triple-spectrum infrared detector for hydrocarbon fires. Ultra-fast mode detects fireballs or explosions within 40 milliseconds; standard-fire response depends on fuel, distance and sensitivity.
- Function: Hydrocarbon flame detector
- Benefit: Detection within 40 milliseconds of fireballs or explosions; detects standard fires 50 ft away within 1.3 seconds, and fires 230 ft away within 3.7 seconds.
- Manufacturer listed standards and approvals: ATEX | IECEx | FM | FMC | CSFM | INMETRO
Technical Specifications
| Brand | Fike |
|---|---|
| Conduit entries | 2 x 3/4 in 14 NPT or M25 x 1.5 |
| Detection range | Standard fires 50 ft (15 m) away within 1.3 seconds |
| Detection technology | Multi-spectrum infrared (IR3) |
| Detector weight (stainless steel 316) | 6.6 lb (3.0 kg) |
| Hazardous area approvals | ATEX II 2 G D Ex db IIC T5/T4 Gb; IECEx; Class I Div. 1 Groups B, C and D; Class I Zone 1 AEx/Ex db IIC |
| Humidity | Up to 99% RH, non-condensing |
| Ingress protection | IP66 and IP68 (2 m, 24 hr); NEMA 4X and 6P |
| Operating temperature | -67°F to +167°F (-55°C to +75°C); -67°F to +185°F (-55°C to +85°C) with the extended option |
| Response time | Within 40 milliseconds of fireballs or explosions |
| Standby current | 120 mA; 180 mA with all systems in operation including window heater |
| Storage temperature | -67°F to +185°F (-55°C to +85°C) |
| Tilt mount weight (stainless steel 316) | 3.3 lb (1.5 kg) |
| Wiring | 12-20 AWG (2.5-0.35 mm2) |