Proreact Fixed Activation Temperature Linear Heat Detection
Linear Heat Detection Cables

Proreact Fixed Activation Temperature Linear Heat Detection

FFE·SKU: FFE-F-PROREACT-FIXED

Fixed-temperature linear heat detection cables for industrial applications, with multiple activation temperatures and protective coverings. Cable, controller and approval must be selected for the application.

Request a quote

Description

Fixed-temperature linear heat detection cables for industrial applications, with multiple activation temperatures and protective coverings. Cable, controller and approval must be selected for the application.

Manufacturer features

  • Fixed Activation
  • Triggers immediately at specific temperatures to ensure timely alarms
  • Durable Construction
  • Designed for rigorous industrial environments
  • Wide Application Range
  • Suitable for various harsh settings including mines and tunnels
  • Interlock Mode
  • Add a double knock to the system installation to reduce false alarms
  • Distance Locating
  • Find an overheat event quickly and easily

This listing covers a manufacturer product family. Select the exact ordering code and approval from the variants below. The FFE-F reference is a catalogue identifier, not a manufacturer part number.

Models and ordering information

  • Nylon: F1070; Stainless Steel: F1078; Activation Temperature: 68⁰C (155⁰F); Approvals: UL, ULC, FM, CE, RoHS
  • Nylon: F1182; Stainless Steel: F1192; Activation Temperature: 68⁰C (155⁰F); Approvals: EN54, CE, RoHS
  • Nylon: F1071; Stainless Steel: F1079; Activation Temperature: 78⁰C (172⁰F); Approvals: UL, ULC, FM, CE, RoHS
  • Nylon: F1180; Stainless Steel: F1190; Activation Temperature: 78⁰C (172⁰F); Approvals: EN54, CE, RoHS
  • Nylon: F1072; Stainless Steel: F1080; Activation Temperature: 88⁰C (190⁰F); Approvals: UL, ULC, FM, CE, RoHS
  • Nylon: F1181; Stainless Steel: F1191; Activation Temperature: 88⁰C (190⁰F); Approvals: EN54, CE, RoHS
  • Nylon: F1073; Stainless Steel: F1081; Activation Temperature: 105⁰C (221⁰F); Approvals: UL, ULC, FM, CE, RoHS
  • Nylon: F1069; Stainless Steel: F1082; Activation Temperature: 185⁰C (365⁰F); Approvals: UL, ULC, FM, CE, RoHS
  • Nylon: F1132; Stainless Steel: F1133; Activation Temperature: 230°C (446°F); Approvals: UL, ULC, FM, CE, RoHS

F1132 and F1133 are nominal 230°C very-high-temperature cables. The technical datasheet lists UL activation at 218°C and FM at 235°C. Select using the applicable approval and installation documentation.

Related accessories and compatibility

  • Part no. UL: A1349; Part No.: A1397; Description: Controller; Compatibility: Fixed Activation Temperature
  • Part no. UL: A1385; Part No.: A1398; Description: End of Line Unit; Compatibility: Fixed Activation Temperature
  • Part no. UL: A1343; Part No.: A1343; Description: Junction Box; Compatibility: Fixed Activation Temperature
  • Part no. UL: A1149-100; Part No.: A1149-100; Description: Ceiling / Wall J-Clip [SS]; Compatibility: Generic
  • Part no. UL: A1362-100; Part No.: A1362-100; Description: Surface P-Clip [Al]; Compatibility: Generic
  • Part no. UL: A1329-100; Part No.: A1329-100; Description: Surface P-Clip [SS]; Compatibility: Generic
  • Part no. UL: A1174-100; Part No.: A1174-100; Description: Cable Tray V-Clip [SS]; Compatibility: Generic
  • Part no. UL: A1175-100; Part No.: A1175-100; Description: Indoor / Outdoor Tiewrap; Compatibility: Generic
  • Part no. UL: A1176-11; Part No.: A1176-11; Description: Indoor Tiewrap (High Temp); Compatibility: Generic
  • Part no. UL: A1177-100; Part No.: A1177-100; Description: Indoor / Outdoor Tiewrap (High Temp); Compatibility: Generic
  • Part no. UL: C1283-100; Part No.: C1283-100; Description: Silicone Sleeves; Compatibility: Generic

Official FFE product information

Technical Specifications

Activation temperatures68, 78, 88, 105, 185°C; VHT models subject to approval-specific ratings
BrandFFE
Cable resistance, standard UL cableApproximately 100 ohms/km per leg; excludes VHT
Controller modelsA1349 / A1397; select by approval and application
Maximum UL cable zone lengthF1070–F1073/F1069 and braided equivalents: 3,000 m; F1132/F1133: 1,000 m
Minimum ambient temperature, UL cable-40°C
Minimum bend radius, UL cable50 mm standard; 63.5 mm F1132/F1133
VHT F1132 / F1133 ratingsUL: 218°C; FM: 235°C per technical datasheet; supplier markets nominal 230°C
Voltage rating, standard UL cable30 Vac / 42 Vdc; not specified here for VHT