Proreact Fixed Activation Temperature Linear Heat Detection
Fixed-temperature linear heat detection cables for industrial applications, with multiple activation temperatures and protective coverings. Cable, controller and approval must be selected for the application.
Request a quoteDescription
Fixed-temperature linear heat detection cables for industrial applications, with multiple activation temperatures and protective coverings. Cable, controller and approval must be selected for the application.
Manufacturer features
- Fixed Activation
- Triggers immediately at specific temperatures to ensure timely alarms
- Durable Construction
- Designed for rigorous industrial environments
- Wide Application Range
- Suitable for various harsh settings including mines and tunnels
- Interlock Mode
- Add a double knock to the system installation to reduce false alarms
- Distance Locating
- Find an overheat event quickly and easily
This listing covers a manufacturer product family. Select the exact ordering code and approval from the variants below. The FFE-F reference is a catalogue identifier, not a manufacturer part number.
Models and ordering information
- Nylon: F1070; Stainless Steel: F1078; Activation Temperature: 68⁰C (155⁰F); Approvals: UL, ULC, FM, CE, RoHS
- Nylon: F1182; Stainless Steel: F1192; Activation Temperature: 68⁰C (155⁰F); Approvals: EN54, CE, RoHS
- Nylon: F1071; Stainless Steel: F1079; Activation Temperature: 78⁰C (172⁰F); Approvals: UL, ULC, FM, CE, RoHS
- Nylon: F1180; Stainless Steel: F1190; Activation Temperature: 78⁰C (172⁰F); Approvals: EN54, CE, RoHS
- Nylon: F1072; Stainless Steel: F1080; Activation Temperature: 88⁰C (190⁰F); Approvals: UL, ULC, FM, CE, RoHS
- Nylon: F1181; Stainless Steel: F1191; Activation Temperature: 88⁰C (190⁰F); Approvals: EN54, CE, RoHS
- Nylon: F1073; Stainless Steel: F1081; Activation Temperature: 105⁰C (221⁰F); Approvals: UL, ULC, FM, CE, RoHS
- Nylon: F1069; Stainless Steel: F1082; Activation Temperature: 185⁰C (365⁰F); Approvals: UL, ULC, FM, CE, RoHS
- Nylon: F1132; Stainless Steel: F1133; Activation Temperature: 230°C (446°F); Approvals: UL, ULC, FM, CE, RoHS
F1132 and F1133 are nominal 230°C very-high-temperature cables. The technical datasheet lists UL activation at 218°C and FM at 235°C. Select using the applicable approval and installation documentation.
Related accessories and compatibility
- Part no. UL: A1349; Part No.: A1397; Description: Controller; Compatibility: Fixed Activation Temperature
- Part no. UL: A1385; Part No.: A1398; Description: End of Line Unit; Compatibility: Fixed Activation Temperature
- Part no. UL: A1343; Part No.: A1343; Description: Junction Box; Compatibility: Fixed Activation Temperature
- Part no. UL: A1149-100; Part No.: A1149-100; Description: Ceiling / Wall J-Clip [SS]; Compatibility: Generic
- Part no. UL: A1362-100; Part No.: A1362-100; Description: Surface P-Clip [Al]; Compatibility: Generic
- Part no. UL: A1329-100; Part No.: A1329-100; Description: Surface P-Clip [SS]; Compatibility: Generic
- Part no. UL: A1174-100; Part No.: A1174-100; Description: Cable Tray V-Clip [SS]; Compatibility: Generic
- Part no. UL: A1175-100; Part No.: A1175-100; Description: Indoor / Outdoor Tiewrap; Compatibility: Generic
- Part no. UL: A1176-11; Part No.: A1176-11; Description: Indoor Tiewrap (High Temp); Compatibility: Generic
- Part no. UL: A1177-100; Part No.: A1177-100; Description: Indoor / Outdoor Tiewrap (High Temp); Compatibility: Generic
- Part no. UL: C1283-100; Part No.: C1283-100; Description: Silicone Sleeves; Compatibility: Generic
Technical Specifications
| Activation temperatures | 68, 78, 88, 105, 185°C; VHT models subject to approval-specific ratings |
|---|---|
| Brand | FFE |
| Cable resistance, standard UL cable | Approximately 100 ohms/km per leg; excludes VHT |
| Controller models | A1349 / A1397; select by approval and application |
| Maximum UL cable zone length | F1070–F1073/F1069 and braided equivalents: 3,000 m; F1132/F1133: 1,000 m |
| Minimum ambient temperature, UL cable | -40°C |
| Minimum bend radius, UL cable | 50 mm standard; 63.5 mm F1132/F1133 |
| VHT F1132 / F1133 ratings | UL: 218°C; FM: 235°C per technical datasheet; supplier markets nominal 230°C |
| Voltage rating, standard UL cable | 30 Vac / 42 Vdc; not specified here for VHT |
Documents & Technical Downloads
Proreact Pocket Guide (EN)
Pocket Guide
Proreact Product Brochure (EN)
Brochure
Proreact Accessories Guide (EN)
Accessories
Related component: Proreact FAT EN Digital Interface Monitor Module Datasheet (EN)
Datasheet
Related component: Proreact FAT UL Digital Interface Monitor Module Datasheet (EN)
Datasheet
Proreact FAT UL LHD Cable Datasheet (EN)
Datasheet
Proreact FAT EN LHD Cable Datasheet (EN)
Datasheet
Related component: Proreact Leader Cable Datasheet (EN)
Datasheet
Related component: Proreact FAT EN End-of-Line-Unit Datasheet (EN)
Datasheet
Related component: Proreact FAT UL End-of-Line-Unit Datasheet (EN)
Datasheet
Related component: Proreact FAT Junction Box Datasheet (EN)
Datasheet
Proreact FAT LHD Cable User Guide (EN)
User Guide
Proreact FAT Sensor Control Unit User Guide (EN)
User Guide
Related component: Proreact FAT Digital Interface Monitor Module User Guide (EN)
User Guide
Proreact Nylon UL Certificate
Approvals
Proreact FM Certificate
Approvals
Proreact UL Certificate
Approvals
Proreact CPR Certificate
Approvals
Proreact VHT FM Certificate
Approvals