Fireray 3000 Ex d Explosion-Proof Beam Smoke Detector
Beam Smoke Detectors

Fireray 3000 Ex d Explosion-Proof Beam Smoke Detector

FFE·SKU: 3000-115

End-to-end infrared beam smoke detector with explosion-proof transmitter and receiver heads and a separate safe-area low-level controller. Detection range: 10–80 m.

Request a quote

Description

End-to-end infrared beam smoke detector with explosion-proof transmitter and receiver heads and a separate safe-area low-level controller. Detection range: 10–80 m.

Models and ordering information

  • Part No.: 3000-115; Description: Fireray 3000 Beam Detector System (Ex d); Approval: ATEX

Related accessories and compatibility

  • Part No.: 1000-019; Description: Fireray 3000 Controller Protective Cage; Compatibility: Specific
  • Part No.: 1150-000; Description: Fireray Commissioning and Maintenance Kit; Compatibility: Generic
  • Part No.: 0209-02; Description: Fireray Test Filter; Compatibility: Generic
  • Part No.: 3000-007; Description: Fireray 3000 Controller; Compatibility: Specific
  • Part No.: 3000-026; Description: Fireray 3000 Detector (Ex d); Compatibility: Specific

Official FFE product information

Technical Specifications

Alarm / fault delay2–30 seconds; EN54-12 compliance restrictions apply
BrandFFE
Controller capacityUp to 2 detector pairs
Controller current14 mA constant, with 1 or 2 receivers
Controller weight606 g
Fire / fault relay contactsVFCO 2 A at 30 Vdc, resistive
IP ratingController: IP54; transmitter / receiver: IP66
Operating range10–80 m
Operating temperature, ATEX-20°C to +55°C, non-condensing
Operating temperature, EN54-12-10°C to +55°C, non-condensing
Optical wavelength850 nm
Relative humidity93%, non-condensing
Response sensitivity25–60%, selectable in 1% steps
Supply voltage12–36 Vdc ±10%
Transmitter / receiver materialCopper-free aluminium alloy LM25
Transmitter / receiver weight3.7 kg each, including brackets
Transmitter current8 mA per transmitter

Documents & Technical Downloads