Sensis Cobalt HM1 / HM2 Aspirating Smoke Detectors
Aspirating Smoke Detection (ASD)

Sensis Cobalt HM1 / HM2 Aspirating Smoke Detectors

FFE·SKU: FFE-F-COBALT-HM

Single- or dual-zone aspirating smoke detectors combining smoke, temperature and humidity monitoring, configurable relays and RS-485 networking.

Request a quote

Description

Single- or dual-zone aspirating smoke detectors combining smoke, temperature and humidity monitoring, configurable relays and RS-485 networking.

Manufacturer features

  • Sub-Zone Specific Configuration
  • HM1 (single pipe), Designed for precise protection of individual areas while the HM2 (dual pipe) enables coverage of two separate sub-zones in a single unit - cost-effective flexibility for varied applications
  • Aspirating Detection with High Sensitivity
  • Built on CSD-H aspirator technology, Cobalt delivers highly sensitive early warning smoke detection, with a wide sensitivity range for dependable performance
  • Compact, Purpose-Built Design
  • Engineered specifically for small to medium open spaces, Cobalt units combine sampling pipes, aspirators, and detection chamber into a single, space-efficient enclosure
  • Network Integration & Output Options
  • Equipped with RS‑485 communication and Modbus RTU support, along with relay outputs, facilitating seamless integration into fire panels and building management systems

This listing covers a manufacturer product family. Select the exact ordering code and approval from the variants below. The FFE-F reference is a catalogue identifier, not a manufacturer part number.

Models and ordering information

  • Part No.: 4100-100; Description: Sensis Cobalt HM1; Approval: EN
  • Part No.: 4200-100; Description: Sensis Cobalt HM2; Approval: EN

The datasheet operating-conditions table specifies a device ambient temperature of 0–40°C. Its separate sensor warning mentions a 60°C ceiling; the 0–100°C sensing range is not a device operating rating.

Related accessories and compatibility

  • Part No.: 4800-000; Description: Sensis Network Interface Module (NIM-1200); Compatibility: All Sensis Detectors
  • Part No.: 4800-001; Description: Sensis Network Control Panel (NCP-1215); Compatibility: All Sensis Detectors
  • Part No.: 4800-002; Description: Sensis In-Line Filter 25mm; Compatibility: All Sensis Detectors
  • Part No.: 4800-003; Description: RS485 to USB Converter; Compatibility: All Sensis Detectors
  • Part No.: 4800-005; Description: Sensis 2.4A Power Supply Unit; Compatibility: All Sensis Detectors. Additional battery box may be required for 2000s models

Official FFE product information

Technical Specifications

Alarm levelsAlert, Action, Fire-1, Fire-2; each delay 0–60 seconds
Alarm sensitivity0.01–20% obs/m
BrandFFE
CommunicationRS-485; Modbus RTU
CurrentHM1: 115–157 mA; HM2: 230–314 mA
Device operating temperature0°C to +40°C
Dimensions, H × W × D321.7 × 154 × 97.4 mm
Event log180,000 events
General purpose inputsHM1: 1; HM2: 2
Humidity sensing range0–100% RH
IP ratingIP51
Maximum coverageHM1: 1,600 m²; HM2: 2,000 m²; subject to approved pipe design
Network devicesUp to 250
Operating humidity10–95% RH, non-condensing
Pipe length, linear / branchedHM1: 105 / 260 m; HM2: 2 × 105 / 2 × 260 m
Relay outputsHM1: 2; HM2: 4; configurable, 2 A at 30 Vdc
Sampling air temperature-20°C to +60°C
Smoke detection range0.02–25% obs/m
Supply voltage24 ±4.8 Vdc
Temperature sensing range0–100°C; distinct from device operating temperature
WeightHM1: 2.2 kg; HM2: 2.3 kg