Flame Detectors
FS20X Flame Detector
Farenhyt·SKU: FAR-F-454331
FS20X is an advanced UV/IR/VIS flame detector offering rapid response, wide-area coverage, and dependable detection of hydrocarbon and non-hydrocarbon fires in challenging conditions.
Request a quoteDescription
Product Overview:
Based on the foundation of the highly successful and reliable SS4 Flame Detector, the FS20X Flame Detector represents a quantum leap in integrating Infrared and Ultraviolet sensing technologies. The FS20X is a Multi-Spectrum and UV/Dual IR/VIS Flame Detector with a proven UV solar-blind sensor. The FS20X exhibits faster false-alarm free response to fires over a wider temperature range and with a much longer detection range compared to conventional UV/IR detectors.
Conventional and older technology UV/IR detectors, using narrow band 4.3 micron IR sensors, will not respond to smoky fires or if the detector lens is contaminated with oil and other substances since both UV and 4.3 micron signals are attenuated, obscured or absorbed by thick smoke or detector lens contaminants. Also, these old technology UV/IR detectors will not alarm to any fire if they are installed behind ordinary window glass.
Dual microprocessors provide a high level of fail-safe operation combined with fast and reliable performance. The Master Microprocessor performs high-speed digital sampling and signal processing calculations: while the slave microprocessor handles various sensor data, performs communications, self-diagnostics and provides interface versatility: and additional memory for storing Event Log and FirePic™ data.
The FS20X Flame Detector has a detection range in excess of 200 feet (very high sensitivity setting) for the detection of a one square-foot Heptane reference fire and has a cone of vision greater in volumetric coverage than most UV/IR detectors. This means fewer detectors can be used as compared to other manufacturers’ detectors.
Additional Features and Benefits:
Based on the foundation of the highly successful and reliable SS4 Flame Detector, the FS20X Flame Detector represents a quantum leap in integrating Infrared and Ultraviolet sensing technologies. The FS20X is a Multi-Spectrum and UV/Dual IR/VIS Flame Detector with a proven UV solar-blind sensor. The FS20X exhibits faster false-alarm free response to fires over a wider temperature range and with a much longer detection range compared to conventional UV/IR detectors.
Conventional and older technology UV/IR detectors, using narrow band 4.3 micron IR sensors, will not respond to smoky fires or if the detector lens is contaminated with oil and other substances since both UV and 4.3 micron signals are attenuated, obscured or absorbed by thick smoke or detector lens contaminants. Also, these old technology UV/IR detectors will not alarm to any fire if they are installed behind ordinary window glass.
Dual microprocessors provide a high level of fail-safe operation combined with fast and reliable performance. The Master Microprocessor performs high-speed digital sampling and signal processing calculations: while the slave microprocessor handles various sensor data, performs communications, self-diagnostics and provides interface versatility: and additional memory for storing Event Log and FirePic™ data.
The FS20X Flame Detector has a detection range in excess of 200 feet (very high sensitivity setting) for the detection of a one square-foot Heptane reference fire and has a cone of vision greater in volumetric coverage than most UV/IR detectors. This means fewer detectors can be used as compared to other manufacturers’ detectors.
Additional Features and Benefits:
- Patented* WideBand IR™ Infrared combined with Ultraviolet
- Detection range greater than 200 feet to 1 sq. ft. heptane fire
- Patented* Electronic Frequency Analysis
- Visible Sensor for optimum false alarm rejection
- Selectable detection sensitivities
- Solar blind 90° full 100% cone-of-vision
- Dual Microprocessors for reliable performance
- Real-time clock for accurate time dating of events
- FirePic™ — Up to 6 pre-fire event data storage
- Event log — Up to 200 events with date and time stamp
- Built-in RS-485 ModBus Communication
- Built-in non-isolated 4-20 mA analog output (sink or source)
- Alarm, Fault and Fire Verification relays.
- Automatic Optical Path and Electronic Self-Test
- Widest operating temperature range
- Patented* Electronics Module for components protection with plug-in terminations for easy field installation
- Two ¾” NPT OR 25mm conduit entries
- Low power consumption
- High RFI and EMI immunity
- FM approved
- Detects hydrocarbon and non-hydrocarbon fuel fires in all environmental conditions
- Arc welding immunity
- False alarm rejection for all environmental conditions
- Minimal maintenance for trouble-free operation
- PC software and Interface Module (FSIM) for fault diagnostics real-time graphs (RTGs), and downloading of FirePics™ and event log
- Suitable for a wide variety of applications.
- Detects hydrocarbon and non-hydrocarbon fuel fires in all environmental conditions
- Range greater than 200 feet to 1 sq. ft. heptane fire
- Arc welding immunity
- Field of view: 90° full 100% core of vision, ± 45° from on axis
- Operating voltage: 24 VDC nominal (18-32 VDC) - regulated
- Sensitivity: Very high, high, medium and low - switch selectable
Elevate your gas detectors’ potential with Honeywell's expert maintenance services! Maximize uptime, eliminate costs, and ensure on-time, on-budget project completion.
Explore our fixed, portable, and high-tech support services now!
Official manufacturer product information
Additional manufacturer specifications
- Warnings & Restrictions: Do Not Use Silicone-Based or Commercial Window Cleaning Products; These will Degrade the Model FS20X Detector Performance; Warning: Potential Electrostatic Charge and Wipe Enclosure Only with a Damp Cloth
- Application: Acetylene Processing and Storage; Aircraft Hangars; Chemical Production, Storage and Loading Facilities; Crude Oil and Gasoline Storage and Tank Farms; Ethanol, Methanol and IPA Production and Storage; Hydrogen Plants and Storage; LNG/LPG Loading and Unloading Facilities; Natural Gas and CNG Plants; Off-Shore Platforms; Oil and Gas Pipelines and Pumping Stations; Paint and Solvent Storage; Refineries and Oil Production Facilities; Turbine/Compressor Enclosures
Technical Specifications
| Alarm Included | Yes |
|---|---|
| Altitude Range | 200ft (60m) |
| Analog Output Signal Type | mA |
| Brand | Honeywell; Honeywell; Notifier |
| Certifications - Regional | Global |
| Communication | FireBus II; ModBus Protocol; RS485 |
| Conduit Entries | (2) 3/4 in NPT |
| Default Relay Activation | Alarm Relay (Relay 1), Auxiliary Relay V (Relay 2), Fault Relay (Relay 3) |
| Enclosure Material | 316 Stainless Steel; Copper-Free Powder Coated Aluminum; Copper-Free Powder Coated Aluminum or 316 Stainless Steel |
| Features | Arc Welding Immunity |
| Field of view | 90° full 100% core of vision, ± 45° from on axis |
| Humidity Range | 5 to 98% RH (Non-Condensing) |
| Industry | Aerospace; Energy; Government & Public Sector; Logistics & Warehouses |
| Ingress Protection | IP66 |
| Loop Resistance | 50 to 400 Ohms; 50 to 400 Ohms |
| Maximum Analog Input Resistance | 400 |
| Maximum Operating Current | 83 mA |
| Minimum Temperature | -40˚C |
| Mounting | Swivel Bracket Assembly |
| Mounting Hole Diameter | 0.25 |
| NEMA Rating | NEMA 4, 4X |
| Number of Digital Communication Ports | 2 |
| Number of Relay Outputs | 3 |
| Operating Current | 85 |
| Operating voltage | 24 VDC nominal (18-32 VDC) - regulated |
| Output Signal Range | 4 to 20 mA |
| Output Signal Type | mA |
| Plug Type | 10 pin for J2 Connector; 6 pin for J1 Connector |
| Relay Activation Settings | Relay 1: Fire Alarm; Relay 2: Fault; Relay 3: Auxiliary |
| Relay Included | Yes |
| Relay Output Configuration | Auxiliary: SPDT (NO/NC); Fault: SPST (NO); Fire Alarm: SPDT (NO/NC) |
| Relay Rated Load | 1A @24V DC |
| Sensing Method | IR, UV |
| Sensitivity | Very high, high, medium and low - switch selectable |
| Spectral Sensitivity | Near Band IR: 0.7 to 1.1 microns; Ultraviolet: 185 to 260 Nanometers; Visible: 400 to 700 Nanometers; Wide Band IR: 1.1 to 3.5 Microns |
| Standards & Certifications | CE: EN6100-6-4 & EN50130-4 |
| Storage Temperature | -55 to +110°C; -55 to 100°C |
| Sub-Category | Flame Detectors; Flame Detectors |
| Vibration | Meets or Exceeds MIL Spec 810C Method 514.2, Curve AW12 |
| Visual Indicators | Green LED: Power; Red LED: Alarm; Yellow: Fault |
| Warranty | 3 Years from Date of Shipment |
| Wireless Technology | WideBand IR™ |
| Wiring | Shielded: 2.5 sq.mm (14 AWG) to 0.326 sq.mm (22 AWG) |