Edwards SIGA-TCDR Temporal Pattern Generator, Fire and CO Tone Module for Signature Sounder Bases
Indicative Price
Excluding local taxes and shipping.
Edwards SIGA-TCDR — Signature Series temporal pattern generator driving fire and carbon monoxide tone patterns on compatible sounder bases.
Description
Edwards SIGA-TCDR — Signature Series temporal pattern generator driving fire and carbon monoxide tone patterns on compatible sounder bases.
Combination smoke and CO detectors must sound two distinct signals. This addressable module generates and synchronizes those patterns for SIGA-AB4GT and SIGA-AB4G-LF bases in Fire-plus-CO mode, which cannot produce them alone. The panel sends channel and sync commands, and the channel picks the pattern.
- Generates TC3, the NFPA 72 fire pattern, and TC4, the NFPA 720 CO tone
- In the US Channel 1 is TC3, Channel 2 is TC4; in Europe the two are reversed
- Uses two addresses on the signaling line circuit, one per channel
- Channel 1 has priority when both are active
- Needs a power limited, regulated 24 VDC fire signaling supply
Despite the name this is not a detector base and no detector mounts on it; Edwards lists it as related equipment to the bases. Pair it with the SIGA-AB4GT or SIGA-AB4G-LF. The SIGA-AB4G is the fire-only base and does not use this module. A SIGA-CRR or SIGA-MCRR polarity reversal relay activates all sounder bases on a loop.