Edwards SIGA-SEC2 Dual Input Security Module, Signature Series
Interface Modules

Edwards SIGA-SEC2 Dual Input Security Module, Signature Series

Edwards·SKU: SIGA-SEC2

Indicative Price

Excluding local taxes and shipping.

Edwards SIGA-SEC2 — intelligent Signature Series module for one or two dry contact security circuits.

infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.

Description

Edwards SIGA-SEC2 — intelligent Signature Series module for one or two dry contact security circuits.

The SEC is literal. Edwards intends this for doors, windows, motion detectors and similar locally powered security devices, not for fire initiating devices. Its duty is set by personality codes from the loop controller, and every code it offers is a security, tamper, maintenance or non-latching active type: 41 through 46, 48 and 3. Disarmed, it treats room activity as a background report; tamper and trouble go through at once.

  • Two input circuits, normally open or normally closed dry contact
  • Requires two Signature addresses; for EST3 loop controllers
  • 720 µA standby, 850 µA tamper or active
  • 1-7/8" × 3" × 1" white Cycoloy enclosure, surface mount on wall or 4" box
  • Wire 16 to 22 AWG; 0° C to 49° C, 0 to 93% humidity non-condensing

The usual mis-order is SIGA-CT2, also a dual input module, but it monitors Class B fire initiating circuits on codes 1 to 4 and mounts to a 1-gang box. SIGA-CT1 is its single circuit version; SIGA-UM is a universal Class A or B module. None offer the security codes.