Edwards SIGA-OSD-IN Signature Optica Intelligent Optical Smoke Detector Head
Indicative Price
Excluding local taxes and shipping.
Edwards SIGA-OSD-IN — Signature Optica intelligent optical smoke detector head for panels using a Signature loop controller.
Description
Edwards SIGA-OSD-IN — Signature Optica intelligent optical smoke detector head for panels using a Signature loop controller.
Edwards datasheet E85001-1001 describes the SIGA-OSD as multi-criteria: it reads several optical sensors at two wavelengths and across multiple scattering angles, then filters the particle data through ratios that strip out patterns typical of nuisance sources such as cooking particulates. It is a head; a Signature base is a separate number, wired first.
- Listed to UL 268 7th edition, UL 268A and CAN/ULC-S529
- Sensitivity range 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) obscuration
- 15.20 to 19.95 VDC; 32 µA normal, 45 µA in alarm
- Five sensitivity settings, twenty pre-alarm settings and environmental compensation
- 32 to 120 °F, 0 to 93 percent RH; air velocity to 4,000 ft. per minute
- Bases SIGA-SB, RB and IB, their SB4, RB4 and IB4 forms, and SIGA-AB4G sounder bases
What the -IN suffix denotes is stated in no Edwards document read for this page: the current catalogue sheet lists SIGA-OSD and SIGA-OSD-NL, the version without a visible logo, and nothing else.