Edwards EST SIGA-MIO Input/Output Module
Interface Modules

Edwards EST SIGA-MIO Input/Output Module

Edwards·SKU: SIGA-MIO

Indicative Price

Excluding local taxes and shipping.

Edwards EST SIGA-MIO — Signature Series plug-in (UIO) input/output module: one supervised Class B input plus one programmable dry-contact relay.

infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.

Description

Edwards EST SIGA-MIO — Signature Series plug-in (UIO) input/output module: one supervised Class B input plus one programmable dry-contact relay.

Edwards calls it simply the plug-in Input/Output Module. It works like the 1-gang SIGA-IO but plugs into a SIGA-UIO2R or SIGA-UIO6R motherboard, where field wiring lands on motherboard terminals. Its function is set by a personality code downloaded from the loop controller.

  • Personality codes 31 through 40, ten selectable: relay with monitor input, alarm input, delayed alarm input, latching or non-latching active input
  • Uses one module address, assigned electronically
  • Monitor-input window 5 to 120 s, 15 s default
  • Relay Form A or B; pilot duty 2 A at 24 Vdc, 0.5 A at 120 Vac
  • 250 µA standby, 430 µA activated; 15.2 to 19.95 Vdc
  • IDC: 47 kΩ EOL, 50 Ω max resistance (25 Ω per wire), 0.1 µF max

SIGA-IO is the same module in a 1-gang mount and will not plug into a motherboard. SIGA-UM is a different device: Class A as well as Class B, covering IDC, NAC and two-wire smoke, and it takes two addresses. SIGA-CT1, CT2 and MCT2 are input-only, with no relay.