Edwards SIGA-IM — Signature Series fault isolator module that keeps a short on the data loop from disabling the entire SLC.
A single short across the two data conductors takes down the whole loop. Isolators bound that loss: wired into a Class A loop, they open on a short so only the segment between two isolators drops out. All isolators open within 23 ms, reclose at 10 ms intervals starting nearest the controller, and the one next to the fault reopens within 10 ms. The loop restores automatically once the short is cleared.
- Uses one detector address; electronic addressing, no dials to set
- 15.2 to 19.95 Vdc (19 Vdc nominal); 45µA standby and activated
- Maximum circuit resistance between isolators 6 Ω
- 2-gang white plate; 2-1/2" (64 mm) deep 2-gang box or SIGA-MP plate
- 18 to 12 AWG; 32°F to 120°F (0°C to 49°C); UL, ULC, CSFM
Class A wiring only, and only with an Edwards Signature loop controller. Edwards later released the SIGA-IM2, so check the panel drawings first.