Edwards SIGA-COD Carbon Monoxide Detector
Indicative Price
Excluding local taxes and shipping.
Edwards SIGA-COD — intelligent addressable carbon monoxide detector for Signature Series loops, sensing carbon monoxide only.
Description
Edwards SIGA-COD — intelligent addressable carbon monoxide detector for Signature Series loops, sensing carbon monoxide only.
The detector converts analog readings from an electrochemical CO cell into digital signals, and an on-board microprocessor tracks them over time, filtering out patterns not typical of a real CO event.
- Electrochemical CO cell with a ten-year life; reports a trouble at end of life
- Listed to UL 2075 and evaluated to the CO alarm sensitivity limits of UL 2034
- Operating voltage 15.20 to 19.95 VDC; 51 µA normal, 68 µA in alarm
- Works only with the Signature Loop Controller; 250 devices per loop
- Mounts on the SIGA-SB, SIGA-RB and SIGA-IB bases and their 4-inch versions
- Sounder bases SIGA-AB4GT and SIGA-AB4G-LF need a SIGA-TCDR tone generator for the CO pattern
- 32 to 120°F, 0 to 90 percent RH noncondensing
The SIGA-COD-CA is the Canadian-market version, listed instead to CAN/CSA 6.19. Do not substitute a Signature Optica SIGA-OSHCD, which adds photoelectric smoke and heat sensing: a job needing smoke detection is not covered by the CO-only SIGA-COD.