Edwards SIGA-AB4GT Sounder Base for Fire and Carbon Monoxide Detectors
Indicative Price
Excluding local taxes and shipping.
Edwards SIGA-AB4GT — Signature Series sounder base carrying both fire and carbon monoxide tone patterns.
Description
Edwards SIGA-AB4GT — Signature Series sounder base carrying both fire and carbon monoxide tone patterns.
An AB4G base fits under any Signature Series detector and shares its address and programming label, so it sounds as a local alarm or as part of a zone. The AB4GT adds the CO case: with a SIGA-TCDR Temporal Pattern Generator on the same loop, its output is field-configurable for Fire Alarm or Fire-plus-CO mode, and the TCDR generates and synchronises the TC3 fire and TC4 carbon monoxide patterns.
- Riser voltage 16 to 33 VDC; supervisory current 1.46 mA DC
- Operating current 31 mA at low dBA and 52 mA at high dBA
- Resonant frequency 3.2 kHz; default high dBA, lowered by a jumper cut
- TC3 fire 86.5 and 90.8 dBA, TC4 CO 77.5 and 84.1 dBA, UL 268 and FM reverberant at 16 VDC
- 6.8 in. diameter, 0.8 in. above the box; UL 268 and UL 464 listed; indoor only, 32 to 120°F
SIGA-AB4G is the fire-only base, not for combination smoke/CO devices in Fire-plus-CO mode. SIGA-AB4G-LF is the 520 Hz version and stands 1.4 in. above the box. The SIGA-TCDR and the AB4G-SB surface box are ordered separately.
Related Products
View Cataloguearrow_forward
Bosch D382 Combustible Gas Detector, 12/24VAC/DC
Indicative Price
from