Edwards SIGA-270P (Manual Pull Fire Alarm)
Indicative Price
Excluding local taxes and shipping.
Manual Pull Fire Alarm Station Two Stage (Presignal), English Markings - UL/ULC Listed
Description
Edwards SIGA-270P — Signature Series single action, two stage presignal manual fire alarm station with general alarm keyswitch, English markings.
Two stage operation separates the first alert from evacuation: the lever sends the presignal and staff escalate with the GA keyswitch. One pull of the teardrop die-cast lever breaks the glass rod and turns in an alarm; the rod deters tampering but is not needed for operation.
- Single action two stage; SIGA-270 is one stage, SIGA-278 double action one stage.
- Uses two module addresses, where SIGA-270 and SIGA-278 each use one.
- Standby 396 µA and activated 680 µA, against 250 and 400 µA one stage.
- 15.2 to 19.95 VDC; terminals 12 to 18 AWG; 32°F to 120°F; UL, ULC, MEA, CSFM and FM.
- Presignal models need a 1-1/2 in. deep 4 in. square box with a 1-gang, 1/2 in. raised cover, not the 2-1/2 in. deep 1-gang box single stage stations use.
The general alarm key is a separate catalogue number, 276-K2 in the USA and 32997 in Canada; Edwards marks only the 276-K1 reset key as supplied. Glass rods 270-GLR and 276-GLR do not interchange with the SIGA-278.
Documents & Technical Downloads
Related Products
View Cataloguearrow_forward
Context Plus Manual Call Point Sounds
Indicative Price
from

Edwards SIGA-278 (Double Action Pull Station)
Indicative Price
from

Gentex CO1209 (918-0009-002) - Replaced by C (918-0030-002)
Indicative Price