Edwards TSD-CJ — SuperDuct four-wire duct smoke detector controller with RJ-45 modular connectors, supplied without a sensor.
Description
Edwards TSD-CJ — SuperDuct four-wire duct smoke detector controller with RJ-45 modular connectors, supplied without a sensor.
A SuperDuct four-wire duct detector is two pieces. The sensor sits on the duct and draws the airstream through a photoelectric chamber; the controller carries the line voltage input, the shutdown relays and the test controls. Edwards states it will not operate until a sensor is connected.
- Drives one or two sensors — TSD-SJ, TSD-SJG or TSD-SJCO2 — by RJ-45 harness, within 15 feet
- Operating voltages: 20 to 29 Vdc, or 24 V, 120 V or 220/240 V at 50/60 Hz
- One normally open alarm contact, 2.0 A at 30 Vdc, for a panel initiating device circuit
- Two Form C auxiliary relays, 10 A at 30 Vdc and 10 A at 250 Vac, for fan and damper control
- One Form C supervision relay, 2.0 A at 30 Vdc; Alarm, Trouble and Power LEDs
- Housing 6.75 x 5.45 x 1.90 inches, rated -4 to 158 °F
TSD-CT is the same controller with terminal blocks instead of RJ-45, TSD-CJG adds a cover gasket, TSD-4WJ combines controller and sensor in one assembly and TSD-SJ is the sensor alone.