Edwards ESD-CJ — SuperDuct four-wire duct smoke detector controller with RJ-45 modular connectors. This is the controller only, not a sensor.

infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.

Description

Edwards ESD-CJ — SuperDuct four-wire duct smoke detector controller with RJ-45 modular connectors. This is the controller only, not a sensor.

In SuperDuct the sensor sits in the duct while the controller holds the relays, status LEDs and line-voltage supply. It will not operate without at least one compatible sensor, and the ESD-CJ pairs only with the ESD-SJ; a working detector also needs a sampling tube sized to the duct. The RJ-45 harness to the sensor may not exceed 15 ft.

  • One normally open alarm initiation contact, 2.0 A at 30 Vdc resistive
  • Two Form C auxiliary relays, 10 A at 30 Vdc / 250 Vac, for HVAC shutdown
  • One Form C supervision relay, 2.0 A at 30 Vdc; aux output 18 Vdc, 30 mA
  • 20 to 29 Vdc, or 24 V, 120 V or 220/240 V at 50/60 Hz; serves one or two sensors
  • At 24 Vdc: 77.9 mA standby, 124.3 mA alarm; -4°F to 158°F; 6.75 × 5.45 × 1.90 in.

Match the letters: TSD-CJ and SD-CJ take TSD-SJ and SD-SJ sensors, ESD-CT is the terminal-block version, ESD-4WJ is controller and sensor in one.