Edwards 757-7A-T Integrity Temporal Horn Strobe, 15/75 cd, 16-33 Vdc or Vfwr, Red, Wall
Horn Strobes

Edwards 757-7A-T Integrity Temporal Horn Strobe, 15/75 cd, 16-33 Vdc or Vfwr, Red, Wall

Edwards·SKU: 757-7A-T

Indicative Price

Excluding local taxes and shipping.

Edwards 757-7A-T — Integrity 757 Series temporal horn strobe, 15/75 cd, red, wall orientation.

infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.

Description

Edwards 757-7A-T — Integrity 757 Series temporal horn strobe, 15/75 cd, red, wall orientation.

The 15/75 is two listings of one fixed output, not two settings. Edwards lists this strobe at 15 cd under UL 1971, the standard for public-mode appliances for the hearing impaired, and at 75 cd under UL 1638, which measures on axis. Nothing is switched: candela is fixed by model, so output is chosen at the order.

  • UL 1971 15 cd wall and 15 cd ceiling; UL 1638 75 cd; CAN/ULC-S526-07 15 cd, 75 cd on axis
  • Rated 17.7 cd at -31 °F (-35 °C)
  • 16 to 33 Vdc or Vfwr; horn and strobe need a constant, not pulsed, signal voltage
  • Strobe typical current 90 mA at 24 Vdc; horn 40 mA high, 20 mA low
  • Jumpers select temporal or steady tone and high or low output; temporal horns self-synchronise within 200 ms on a common circuit, but strobe flash needs a G1M-RM, SIGA-CC1S or BPS booster to meet UL 1971

Ships with the LKW-1 FIRE wall lens; LKC kits give ceiling markings. The candela siblings share this body: 757-5A-T 15 cd, 757-3A-T 30 cd, 757-4A-T 75 cd and 757-8A-T 110 cd; 757-1A-T is the horn alone. Add -W for white.